2016-08-09 08:07:272ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS AND NEW PER SCOPE NOW SHOWN REGARDING
 INSTA HOT 18KV:
  
 2. PROVIDE AIC CALCULATIONS FOR NEW SERVICE PER FBC RES
 E3606
 1. SHOW AIC RATING ON PANEL SCHEDULE. FBC RES E3606
 2. CORRECT INSTA HOT 18KV ON CALCULATION SUBMITTED, ON
 PANEL SCHEDULE AND LOADS. PANEL SCHEDULE SHOWS 4500W.
 CALCULATIONS SHOW 5000, CORRECT A SUBMIT REFLECTING
 18,000W. VERIFY 200AMP SERVICE IS SUFFICIENT.
 6. FEEL FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  