2016-03-12 05:17:23INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. UPDATE ALL APPLICABLE CODES ON GENERAL NOTES TO
 REFLECT NEW FBC 2014 5TH EDITION SET AND NFPA 70 NEC
 2011.
 2. PROVIDE AIC CALCULATIONS FOR NEW SERVICE PER FBC RES
 E3606
 3. PROVIDE A NOTE TO INDICATE THE REQUIREMENTS OF FBC
 RES 404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS.
 4. SHOW ON PANEL SCHEDULE THE CONDUCTOR SIZE FOR THE
 WATER HEATER. NEC 310.15B16
 5. PER FBC RES E3706, SHOW AND LABEL BRANCH CIRCUITS ON
 PANEL BOARDS SPECIFIC AREA AS TO WHAT IT SERVES.
 GENERAL LIGHTING DESIGNATION WILL NOT SUFFICE. MUST BE
 CLEAR AND EVIDENT AS TO WHAT IT ENERGIZES.
 6. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  
  
  