Date |
Text |
2016-04-11 13:23:48 | 07/27/16: |
| TALKED TO MICHELLE (PBC IMPACT FEES) TOTAL NEW A/C AREA |
| 754 S.F. AND TOTAL NEW PORCH AREA 247S.F. (AREA |
| CALCULATIONS DONE ON PENCIL ON DRAWING A-5). ACCORDING |
| TO PAPA AND CITY RECORDS THE BASE AREA WAS 854 S.F. THE |
| REST WAS ENCLOSED PORCH, FINISHED PORCH, UNFINISHED |
| STORAGE AND FINISHED STORAGE. TOTAL WAS 1360 S.F. SEE |
| PAPA). JG. |
| |
| |
| RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC-5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- GENERAL NOTES ON SHEET A-1 REFERENCE 2010 FBC. THE |
| CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH EDITION |
| (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA |
| STATUTES. |
| |
| 3- SHEET A-2: |
| A) STRUCTURAL DESIGN CRITERIA AND CODES REFERENCE 2010 |
| FBC. THE CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH |
| EDITION (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA |
| STATUTES. |
| |
| B) UPDATE YEAR FOR ALL THE REFERENCE STANDARDS SHOWN ON |
| SHEET A-2. SEE CHAPTER 46 FBC-RESIDENTIAL, 5TH EDITION |
| (2014) FOR CURRENT YEAR AND REVISE AS REQUIRED. FOR |
| EXAMPLE THE CURRENT ACI EDITION IS THE ACI-11 NOT |
| ACI-95. |
| |
| C) FLOOR AND ROOF LIVE LOADS SHOWN ON THE STRUCTURAL |
| DESIGN CRITERIA & CODES DOESN'T MATCH LOADS SHOWN ON |
| THE PRE-ENGINEERED WOOD TRUSSES NOTES ON SAME SHEET. |
| SEE FOOTNOTES "B" AND "G" OF TABLE R301.5 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS |
| REQUIRED TO MATCH. |
| |
| D) THE CURRENT ASCE 7 IS THE ASCE 7-10 NOT ASCE 7-98 |
| REVISE THE PRE-ENGINEERED WOOD TRUSSES NOTES. CHAPTER |
| 553 F.S. |
| |
| E) REVISE NAIL SIZE AND TYPE SPECIFIED FOR THE PLYWOOD |
| SHEATHING. SEC. R803.2.3.1 REQUIRES 8 D RING SHANK |
| NAILS. OR PROVIDE ENGINEER ANALYSIS SHOWING THAT THE |
| 10D NAILS ARE EQUIVALENT TO THE 8D RING SHANK NAILS. |
| |
| 4- SHEET A-4: |
| A) UPDATE CODE. THE CURRENT CODE IS THE |
| FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS |
| REQUIRED. CHAPTER 553 FLORIDA STATUTES. ALSO, UPDATE |
| THE LOADING NOTES AT THE BOTTOM OF THIS SHEET. |
| |
| B) CLARIFY THE SOIL BEARING CAPACITY 2500 PSI OR 2500 |
| PSF. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $90,000. THE |
| PERMIT FEE BALANCE IS $2148.70. |
| |
| 6- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION AT NEW |
| ADDITION TO COMPLY WITH SEC. R807 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| 8- SHEET A-6. SPECIFY BEAMS AT THE NEW COVERED PORCH. |
| AND, SPECIFY CONNECTORS AT THE ENDS OF EACH BEAM. SEC. |
| R801.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 9- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET |
| A-7 DON'T MATCH DESIGN PRESSURES SPECIFIED ON SHEET |
| A-2. REVISE AS REQUIRED. SEC. R301 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| 10- PROVIDE COMPLETE WALL SECTION THRU GABLE END |
| SHOWING COMPLIANCE WITH SEC. R609.4 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| 11- SHEET A-6: SEC. R4409.13.3.2.5 SPECIFIED FOR |
| UNVENTED ATTIC APPLIES TO THE HIGH VELOCITY AREAS ONLY. |
| IF DESIGNING AN UNVENTED ATTIC, THEN SEE SEC. R806.5 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS |
| REQUIRED. |
| |
| 12- TYPICAL WALL SECTION ON SHEET A-7: |
| A) CLEARLY SPECIFY TYPE AND LOCATION OF INSULATION. |
| NOTE: COORDINATE WITH UNVENTED ATTIC AND ITEM #11 |
| ABOVE. SEC. R806.5 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| B) PROVIDE COMPLETE SPECIFICATIONS FOR THE TIE BEAM. |
| SEC. R801.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 13- PROVIDE ICC EVALUATION REPORT FOR THE TYPE OF |
| INSULATION SPECIFIED ON ITEM #12(A) ABOVE. SEC. R316 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 14- ROOF FRAMING NOTES ON SHEET A-7 REFERENCE 2010 FBC. |
| THE CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH EDITION |
| (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA |
| STATUTES. |
| |
| 15- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM |
| WINDOWS TO BE REPLACED AND TYPE AND SIZE OF PROPOSED |
| WINDOWS TO VERIFY EGRESS REQUIREMENTS OF SEC. 704 OF |
| FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| |
| 16- SPECIFY CARBON MONOXIDE ALARM BY THE NEW MASTER |
| BEDROOM AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) METAL ROOF AS SPECIFIED ON PLANS. |
| |
| B) ALL WINDOW TYPES AS SPECIFIED ON PLANS. |
| |
| C) INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| |
| D) OUTSWING FRENCH DOORS AS SHOWN ON PLANS. |
| |
| E) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS. |
| PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| AND PAGE SHOWING THE CONNECTOR OR LIST THE FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| |
| F) PRECAST LINTELS (IF SPECIFIED ON PLANS) |
| |
| G) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT |
| GLASS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| |
| 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| CITY AMENDMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T |
| STAPLE OLD DRAWINGS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |