Plan Review Notes
Plan Review Notes For Permit 16030347
Permit Number 16030347
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-11 13:23:4807/27/16:
 TALKED TO MICHELLE (PBC IMPACT FEES) TOTAL NEW A/C AREA
 754 S.F. AND TOTAL NEW PORCH AREA 247S.F. (AREA
 CALCULATIONS DONE ON PENCIL ON DRAWING A-5). ACCORDING
 TO PAPA AND CITY RECORDS THE BASE AREA WAS 854 S.F. THE
 REST WAS ENCLOSED PORCH, FINISHED PORCH, UNFINISHED
 STORAGE AND FINISHED STORAGE. TOTAL WAS 1360 S.F. SEE
 PAPA). JG.
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- GENERAL NOTES ON SHEET A-1 REFERENCE 2010 FBC. THE
 CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA
 STATUTES.
  
 3- SHEET A-2:
 A) STRUCTURAL DESIGN CRITERIA AND CODES REFERENCE 2010
 FBC. THE CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA
 STATUTES.
  
 B) UPDATE YEAR FOR ALL THE REFERENCE STANDARDS SHOWN ON
 SHEET A-2. SEE CHAPTER 46 FBC-RESIDENTIAL, 5TH EDITION
 (2014) FOR CURRENT YEAR AND REVISE AS REQUIRED. FOR
 EXAMPLE THE CURRENT ACI EDITION IS THE ACI-11 NOT
 ACI-95.
  
 C) FLOOR AND ROOF LIVE LOADS SHOWN ON THE STRUCTURAL
 DESIGN CRITERIA & CODES DOESN'T MATCH LOADS SHOWN ON
 THE PRE-ENGINEERED WOOD TRUSSES NOTES ON SAME SHEET.
 SEE FOOTNOTES "B" AND "G" OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS
 REQUIRED TO MATCH.
  
 D) THE CURRENT ASCE 7 IS THE ASCE 7-10 NOT ASCE 7-98
 REVISE THE PRE-ENGINEERED WOOD TRUSSES NOTES. CHAPTER
 553 F.S.
  
 E) REVISE NAIL SIZE AND TYPE SPECIFIED FOR THE PLYWOOD
 SHEATHING. SEC. R803.2.3.1 REQUIRES 8 D RING SHANK
 NAILS. OR PROVIDE ENGINEER ANALYSIS SHOWING THAT THE
 10D NAILS ARE EQUIVALENT TO THE 8D RING SHANK NAILS.
  
 4- SHEET A-4:
 A) UPDATE CODE. THE CURRENT CODE IS THE
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED. CHAPTER 553 FLORIDA STATUTES. ALSO, UPDATE
 THE LOADING NOTES AT THE BOTTOM OF THIS SHEET.
  
 B) CLARIFY THE SOIL BEARING CAPACITY 2500 PSI OR 2500
 PSF. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $90,000. THE
 PERMIT FEE BALANCE IS $2148.70.
  
 6- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION AT NEW
 ADDITION TO COMPLY WITH SEC. R807 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 8- SHEET A-6. SPECIFY BEAMS AT THE NEW COVERED PORCH.
 AND, SPECIFY CONNECTORS AT THE ENDS OF EACH BEAM. SEC.
 R801.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 9- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET
 A-7 DON'T MATCH DESIGN PRESSURES SPECIFIED ON SHEET
 A-2. REVISE AS REQUIRED. SEC. R301 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 10- PROVIDE COMPLETE WALL SECTION THRU GABLE END
 SHOWING COMPLIANCE WITH SEC. R609.4 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 11- SHEET A-6: SEC. R4409.13.3.2.5 SPECIFIED FOR
 UNVENTED ATTIC APPLIES TO THE HIGH VELOCITY AREAS ONLY.
 IF DESIGNING AN UNVENTED ATTIC, THEN SEE SEC. R806.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS
 REQUIRED.
  
 12- TYPICAL WALL SECTION ON SHEET A-7:
 A) CLEARLY SPECIFY TYPE AND LOCATION OF INSULATION.
 NOTE: COORDINATE WITH UNVENTED ATTIC AND ITEM #11
 ABOVE. SEC. R806.5 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE TIE BEAM.
 SEC. R801.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- PROVIDE ICC EVALUATION REPORT FOR THE TYPE OF
 INSULATION SPECIFIED ON ITEM #12(A) ABOVE. SEC. R316 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 14- ROOF FRAMING NOTES ON SHEET A-7 REFERENCE 2010 FBC.
 THE CURRENT CODE IS THE FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE AS REQUIRED. CHAPTER 553 FLORIDA
 STATUTES.
  
 15- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOWS TO BE REPLACED AND TYPE AND SIZE OF PROPOSED
 WINDOWS TO VERIFY EGRESS REQUIREMENTS OF SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 16- SPECIFY CARBON MONOXIDE ALARM BY THE NEW MASTER
 BEDROOM AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) METAL ROOF AS SPECIFIED ON PLANS.
  
 B) ALL WINDOW TYPES AS SPECIFIED ON PLANS.
  
 C) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 D) OUTSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 E) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE CONNECTOR OR LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 F) PRECAST LINTELS (IF SPECIFIED ON PLANS)
  
 G) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT
 GLASS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]