Plan Review Notes
Plan Review Notes For Permit 16030336
Permit Number 16030336
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-10 18:35:02REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
  
 - PROVIDE MANUFACTURE SHEETS ON SLAT GENERATOR FOR
 ELECTRICAL INFORMATION.
  
 - SHOW A FEEDER DIAGRAM OF POOL EQUIPMENT WITH PANEL
 SCHEDULE
  
 - IF THIS IS A PLUG IN UNIT CLARIFY BREAKER SIZE AND
 GFCI PROTECTION.