Plan Review Notes For Permit 16030329 |
Permit Number |
16030329 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-16 09:57:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. THERE IS INSUFFICIENT DETAIL TO PROPERLY REVIEW AND | | APPROVE THIS SUBMITTED PLAN. | | | | 2. PROVIDE A SITE PLAN INDICATING THE LOCATIONS OF ALL | | EQUIPMENT AND DIMENSIONS TO ALL BUILDINGS AND | | EQUIPEMNT. | | | | 3. PROVIDE ALL EQUIPMENT SPECIFICATION DETAILS, PRODUCT | | SHEETS. | | | | WHAT IS "EXPLOSION PROOF J.B. DISPENSOR"? | | | | WHAT IS " EXPLOSION PROOF EM SHUT OFF"? | | | | WHAT IS " SHUNT SQD 200A2P BLKER"? | | | | 4. THE DESIGN AND INSTALLATION SHALL COMPLY WITH THE | | APPROPRIATE NFPA FIRE CODES INCLUDING, BUT NOT LIMITED | | TO, NFPA 58, LIQUEFIED PETROLEUM GAS CODE; THE PROPOSED | | PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION | | OF FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012 | | EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE | | CODES OR STANDARDS, AND FLAMMABLE AND COMBUSTIBLE | | LIQUIDS SHALL COMPLY WITH NFPA 30, 2012 EDITION. | | | | 5. PROVIDE THE LOCATION OF THE NEAREST FIRE | | EXTINGUISHER, WITHIN 75'. | | | | 6. PROVIDE A BRIEF NARRATIVE OR STATEMENT REGARDING | | WHAT PURPOSE/SERVCIE THIS INSTALLATION PROVIDES. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|