2016-03-10 10:12:42 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1.PER FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ALSO SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF WORK PROPOSED. SHOW IN |
| DETAIL THAT IT WILL CONFORM TO CODE. |
| 2.INFORMATION PROVIDED IS VERY VAGUE. THE FOLLOWING IS |
| REQUIRED TO BE PROVIDED. |
| 3.PROVIDE LOCATION OF PANEL BOARD AND RATING WHERE |
| POWER WILL ORIGINATE TO PROPANE DISPENSER MOTOR. FBC |
| 107.3.5 |
| 4.SHOW ON PLANS REQUIRED SEAL OFF INSTALLATION FROM |
| CLASSIFIED AREA BOUNDARIES. FBC 107.3.5 |
| 5.SHOW THE ROUTING OF UNDERGROUND CONDUIT TO VERIFY |
| DEPTH OF INSTALLATION. NEC 300.5 |
| 6.CLARIFY EMT BEING INSTALLED IN CLASS 1 LOCATION; IS |
| IT IN THE SHOP AREA? |
| 7.SHOW NOTES TO COMPLY WITH NEC 514.11 DISCONNECTS AND |
| 514.16 BONDING AND GROUNDING |
| 8.SHOW ON FLOOR PLAN WHERE THE DISCONNECT WILL BE |
| MOUNTED AND THE DISTANCE FROM DISPENSER. NEC 514.11 |
| 9.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL |
| FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE |
| ANY QUESTIONS OR CONCERNS. |
| |