Plan Review Notes For Permit 16030242 |
Permit Number |
16030242 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-09 04:03:33 | 1) THE PLANS ARE CONFUSING AS TO THE SCOPE OF | | WORK.SHT.A100.0 FLOOR PLAN IS DIFFERENT FROM | | A101.0.BOTH FLOOR PLANS ARE LISTED AS "REVISED".WHICH | | LAYOUT IS BEING BUILT? SUBMIT ONE FLOOR PLAN THAT | | CLEARLY REFLECTS THE SCOPE OF WORK TO BE DONE. FBC | | 107.2.1. | | 2) A MINIMUM OF 21 INCHES CLEARANCE IS REQUIRED IN | | FRONT OF WATER CLOSETS.THE LAVATORY IN THE FIRST FLOOR | | BATH CLEARLY ENCROACHES INTO THIS CLEAR FLOOR | | SPACE.FBCR P2705.1 (5). | | 3) WATER SUPPLY VALVES FOR THE WASHER/DRYER UNIT MUST | | BE ACCESSIBLE. THEY CANNOT BE LOCATED BEHIND THE | | WASHER/DRYER UNLESS THERE IS AN ACCESS PANEL IN THE | | WASHER/DRYER UNIT THAT CAN BE REMOVED FOR ACCESS TO THE | | VALVES. FBCR SEC.P2903.9.3. | | 4)SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWER. THE | | SHOWER SIZE SHALL COMPLY WITH FBCR SEC.P2708.1. | | 5) SHT. A204 SHOWS A BATHTUB IN THE BATHROOM BUT THERE | | ARE TWO DIFFERENT FLOOR PLANS. ONE SHOWS A TUB AND THE | | OTHER A SHOWER. WHICH IS IT? FBCR107.2.1. | | 6) SHT. D100.0 NOTES THE REMOVAL OF PLUMBING FIXTURES | | AND "REPLACE ALL IN KIND" BUT FIXTURES ARE BEING | | RELOCATED AND CHANGED.CLARIFY. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|