2016-10-31 07:53:02 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16030222 |
| ADD: 5400 EAST AVENUE |
| CONT: STUART & SHELBY DEVELOPMENT |
| TEL: 561-637-7902 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| |
| 4TH REVIEW |
| DATE: MON. OCT. 31/ 2016 |
| ACTION: DENIED |
| |
| NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH RESPECT |
| TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| |
| 1-3) COMPLIED. |
| |
| 4A) 4TH REQUEST!!!!!! THE CITY IS IN RECEIPT OF THE |
| FLOOD ZONE CERTIFICATE FOR 5400 EAST AVE. SURVEYORS |
| NAME: JAMES G. PEDEN, JR. DATED 6/12/2015. PLEASE NOTE |
| THIS CERTIFICATE IS NOT SIGNED NOR SEALED BY THE |
| SURVEYOR. SURVEYORS: F. S. 472.025 SEALS. THE FINISH |
| FLOOR IS GIVEN AT ELEVATION 17.1 FT. NGVD. PLEASE ALSO |
| NOTE THE SUBMITTED |
| ELEVATION CERTIFICATE IS ALSO MARKED FINISH |
| CONSTRUCTION SEE LINE C1 OF CERTIFICATE. THIS 1ST |
| ELEVATION CERTIFICATE SHOULD BE MARKED CONSTRUCTION |
| DRAWINGS. THE CERTIFICATE SHOULD READ CONSTRUCTION |
| DRAWINGS. |
| |
| |
| |
| 4B-E) COMPLIED. |
| |
| 1ST ROUND COMMENT. 4) PLEASE NOTE THIS PROPERTY IS |
| LOCATED WITHIN AN AH FLOOD ZONE. FBC BUILDING 1612 AND |
| CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| ADDITIONAL 6 INCHES OF ELEVATION. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31/2015 |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 5-8) COMPLIED. |
| |