2016-06-03 10:32:482ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030222
 6/3/16
  
 1) PROVIDE THE MODEL NUMBER AND EQUIPMENT SCHEDULE FOR
 THE NEW ERV IN THE DINING ROOM.
  
 2) SHEETS M1.1 & M3.1: THE SUPPLY CFMS FOR RTU'S 4 & 7
 DO NOT MATCH.
  
 3) M1.1 & M2.1: THE EXHAUST RATE FOR THE FANS IN THE
 MEN'S RRM 12 & WOMEN'S RRM 13 MUST BE 70 CFM'S EACH PER
 TABLE 403.3. THESE DO NOT APPEAR TO BE PRIVATE TOILET
 ROOMS.
  
 4) THE DESIGN PROFESSIONAL MUST COMPLETE HIS PORTION OF
 THE MANDATORY REQUIREMENTS CHECKLIST ON PAGE 9 OF THE
 ENERGY GAUGE IECC COMPLIANCE SUBMITTAL.
  
 5) THE SUBMITTED WIND LOAD ENGINEERING FOR THE RTU'S
 AND CURBS IS IN COMPLETE: A) THE SUBMITTAL IS ONLY FOR
 THE LENNOX UNIT- RTU-9, THE CARRIER UNIT- RTU-7 WAS NOT
 INCLUDED. B) THE LENNOX SUBMITTAL DOES NOT INCLUDE THE
 CURB AND CURB ATTACHMENT TO THE STRUCTURE. C) THE
 SUBMITTAL WAS A COPY AND DID NOT HAVE AN ORIGINAL
 SIGNATURE AND SEAL FROM THE PE AS REQUIRED BY FLORIDA
 STATUTE AND FAC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER