2016-06-03 10:32:48 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #16030222 | | 6/3/16 | | | | 1) PROVIDE THE MODEL NUMBER AND EQUIPMENT SCHEDULE FOR | | THE NEW ERV IN THE DINING ROOM. | | | | 2) SHEETS M1.1 & M3.1: THE SUPPLY CFMS FOR RTU'S 4 & 7 | | DO NOT MATCH. | | | | 3) M1.1 & M2.1: THE EXHAUST RATE FOR THE FANS IN THE | | MEN'S RRM 12 & WOMEN'S RRM 13 MUST BE 70 CFM'S EACH PER | | TABLE 403.3. THESE DO NOT APPEAR TO BE PRIVATE TOILET | | ROOMS. | | | | 4) THE DESIGN PROFESSIONAL MUST COMPLETE HIS PORTION OF | | THE MANDATORY REQUIREMENTS CHECKLIST ON PAGE 9 OF THE | | ENERGY GAUGE IECC COMPLIANCE SUBMITTAL. | | | | 5) THE SUBMITTED WIND LOAD ENGINEERING FOR THE RTU'S | | AND CURBS IS IN COMPLETE: A) THE SUBMITTAL IS ONLY FOR | | THE LENNOX UNIT- RTU-9, THE CARRIER UNIT- RTU-7 WAS NOT | | INCLUDED. B) THE LENNOX SUBMITTAL DOES NOT INCLUDE THE | | CURB AND CURB ATTACHMENT TO THE STRUCTURE. C) THE | | SUBMITTAL WAS A COPY AND DID NOT HAVE AN ORIGINAL | | SIGNATURE AND SEAL FROM THE PE AS REQUIRED BY FLORIDA | | STATUTE AND FAC. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|