2016-06-16 13:31:39 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16030222 |
| ADD: 5400 EAST AVENUE |
| CONT: STUART & SHELBY DEVELOPMENT |
| TEL: 561-637-7902 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. JUNE 16/ 2016 |
| ACTION: DENIED |
| |
| 1)SHEET A9 INDICATES THE WINDOW AND EXTERIOR DOOR |
| POSITIVE & NEGATIVE PRESSURES. PLEASE PROVIDE WHERE THE |
| WIND DESIGN CRITERIA CAN BE LOCATED IN THE PLANS. |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| |
| |
| 2A) SEMI- REQUIRED, PLEASE CIRCLE WHICH APPLICATION |
| METHOD WILL BE USED TO INSTALL THIS TYPE SHUTTER. |
| SHEET A7 SHOWS A WHITE BAHAMA STYLE SHUTTER, PLEASE |
| PROVIDE IF THIS RIGID AWNING WILL STAY AS POSITIONED OR |
| REPOSITIONED TO CLOSE AN OPENING WHEN THE BUILDING IS |
| UNATTENDED OR ACT AS A STORM SHUTTER, THE DESIGN IN THE |
| CLOSED POSITION SHALL ALSO COMPLY WITH CHAPTER 16 AND |
| SHALL BE IMPACT RESISTANT IN ACCORDANCE WITH SECTION |
| 1609.1.2 FBC-B. |
| |
| 2B) NEW COMMENT. SUBMITTED FLORIDA PRODUCT APPROVAL |
| TRULITE 351 SERIES ALUM OUTSWING DRY GLAZED DOORS FL# |
| 17086 DOES NOT HAVE THE FLORIDA COVERSHEET SHOWING IT |
| IS STILL AN APPROVED REPORT. THIS REPORT NOT LISTED ON |
| THE FLORIDA APPROVAL WEBSITE. COMPLIANCE WITH 2014 |
| FBC-B 1609.4.4.1. |
| |
| 3) COMPLIED. 2008 MIST DRYSTACK LEDGESTONE OWENS |
| CORNING. |
| |
| 4A) FLOOD ZONE COMMENT. THE CITY IS IN RECEIPT OF THE |
| FLOOD ZONE CERTIFICATE FOR 5400 EAST AVE. SURVEYORS |
| NAME: JAMES G. PEDEN, JR. DATED 6/12/2015. PLEASE NOTE |
| THIS CERTIFICATE IS NOT SIGNED NOR SEALED BY THE |
| SURVEYOR. SURVEYORS: F. S. 472.025 SEALS. THE FINISH |
| FLOOR IS GIVEN AT ELEVATION 17.1 FT. NGVD. |
| |
| 4B) THE CITY HAS ALSO REVIEWED THE BUILDING EVALUATION |
| REPORT PREPARED BY BOYLE & DRAKE INC. LISTING THE |
| MARKET VALUE OF THE STRUCTURE AT $2,435,000.00 DOLLARS. |
| 50% OF THE MARKET VALUE IS $1,217,500.00 DOLLARS. |
| |
| 4C) THE CITY?S MUNI CODE UNDER THE DEFINITION OF |
| SUBSTANTIAL IMPROVEMENT IS FOUND UNDER ARTICLE XIX |
| DEFINITIONS, SECTION 94-611. |
| SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF |
| REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO |
| A STRUCTURE, TAKING PLACE DURING THE LIFE OF A |
| STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR |
| EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE |
| STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE |
| THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START |
| OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF |
| DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE |
| OCCURRING. FOR THE PURPOSES OF THIS DEFINITION, |
| "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN |
| THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR |
| OTHER STRUCTURAL PART OF THE BUILDING COMMENCES, |
| WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL |
| DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL |
| IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT |
| OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH, |
| SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO |
| ENSURE SAFE LIVING CONDITIONS. |
| |
| 4D) SINCE SUBSTANTIAL IMPROVEMENT HAS BEEN MET WITH THE |
| RENOVATION PERMIT (01040625/ VALUE OF |
| $150,000.00)TO THIS BUILDING. $1,075,000 (APPLIED |
| PERMIT VALUE) + $150,000.00 = $ 1,225,000.00 WHICH IS |
| GREATER THAN $1,217,500.00 OR 50% OF THE STRUCTURE |
| SUBSTANTIAL IMPROVEMENT HAS BEEN MET. |
| |
| 4E) SINCE IS A COMMERCIAL BUILDING ( NONRESIDENTIAL) |
| FLOOD PROOFING IS A OPTION TO MEET CODE COMPLIANCE. |
| WEST PALM BEACH MUNI CODE: |
| SEC. 94-546 (B) AREAS OF SPECIAL FLOOD HAZARD WITH BASE |
| FLOOD ELEVATION PROVIDED. (2) NONRESIDENTIAL |
| CONSTRUCTION. |
| ALL NEW CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT OF ANY |
| COMMERCIAL, INDUSTRIAL OR OTHER NONRESIDENTIAL |
| STRUCTURE SHALL EITHER HAVE THE LOWEST FLOOR, INCLUDING |
| BASEMENT, ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE |
| BASE FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT |
| UTILITY AND SANITARY FACILITIES, BE FLOODPROOFED SO |
| THAT BELOW SIX INCHES ABOVE THE FLOOD BASE LEVEL THE |
| STRUCTURE IS WATERTIGHT, WITH WALLS SUBSTANTIALLY |
| IMPERMEABLE TO THE PASSAGE OF WATER AND WITH STRUCTURAL |
| COMPONENTS HAVING THE CAPABILITY OF RESISTING |
| HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF |
| BUOYANCY. A REGISTERED PROFESSIONAL ENGINEER OR |
| ARCHITECT SHALL CERTIFY THAT THE STANDARDS OF THIS |
| SUBSECTION ARE SATISFIED. SUCH CERTIFICATION SHALL BE |
| PROVIDED TO THE CITY ENGINEER. |
| |
| 1ST ROUND COMMENT. 4) PLEASE NOTE THIS PROPERTY IS |
| LOCATED WITHIN AN AH FLOOD ZONE. FBC BUILDING 1612 AND |
| CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| ADDITIONAL 6 INCHES OF ELEVATION. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31/2015 |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 5)SEMI-COMPLIED. THE SUBMITTED WIND ENGINEERING FOR THE |
| RTU'S AND CURBS IS INCOMPLETE. |
| A) THE SUBMITTAL IS ONLY FOR THE LENNOX UNIT RTU-9. THE |
| CARRIER UNIT RTU-7 WAS NOT INCLUDED. |
| B) THE LENNOX SUBMITTAL DOES NOT INCLUDE THE CURB AND |
| CURB ATTACHMENT TO THE STRUTURE. |
| C) THE SUBMITTAL WAS A COPY AND DID NOT HAVE AN |
| ORIGINAL SIGNATURE AND SEAL. FL ADMIN CODE 61G15-23.002 |
| ENGINEERS. |
| |
| COMMENT 1ST ROUND REVIEW, SHEET M1.1 SHOWS A NEW ROOF |
| TOP RTU # 9 PLEASE PROVIDE ENGINEERING FOR THE FRAMING |
| AROUND THE NEW ROOF TOP HOLE FOR THIS UNIT. ALSO |
| PROVIDE THE MANUFACTURERS INSTALLATION INSTRUCTIONS, IF |
| A PRODUCT APPROVAL PLEASE PROVIDE AS WELL AS THE TIE |
| DOWN OF THE RTU TO THE CURB. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31(D) ROOFING PRODUCTS AND ASSEMBLIES/ CURBS/ ROOF TOP |
| FANS |
| FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM |
| THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014 |
| FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 6) COMPLIED. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 7) COMPLIED. NOT REQUIRED. FBC-B 1509.6 MECHANICAL |
| EQUIPMENT SCREENS. |
| |
| 8) COMPLIED. 2014 FBC-ACCESSIBILITY CODE904.5.2 TRAY |
| SLIDES. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |