Plan Review Notes
Plan Review Notes For Permit 16030222
Permit Number 16030222
Review Stop P
Sequence Number 1
Notes
Date Text
2016-03-16 14:57:361) SHT. A-2 - TOILET ROOM CALCULATIONS - THE TABLE
 REFERENCED IS INCORRECT. THERE IS NO TABLE 400.1 IN THE
 2014 FLORIDA PLUMBING CODE. THE CORRECT TABLE IS 403.1.
 PLEASE CORRECT.
 2) CLEARLY SHOW THE LOCATION OF THE REQUIRED SERVICE
 SINKS FOR THE INSTITUTIONAL AND ASSEMBLY OCCUPANCIES AS
 REQUIRED BY 2014 FPC TABLE 403.1.
 3) A MINIMUM OF ONE NEW WASHER AND ONE NEW DRYER IN THE
 EXISTING LAUNDRY AREA SHALL COMPLY WITH THE 2014 FBC
 ACCESS. SEC.611.1 - 611.4.
 4) SHT. A-11, DETAIL #2 - SHOW THE REQUIRED 30 INCH
 WIDE MINIMUM BY 60 INCH LONG MINIMUM CLEAR FLOOR SPACE
 ADJACENT TO THE OPEN FACE OF THE ACCESSIBLE SHOWER.
 5) GRAB BARS IN THE ACCESSIBLE ROLL-IN SHOWER WITH THE
 SEAT SHALL BE LOCATE DIN ACCORDANCE WITH THE 2014 FAC
 SEC.608.3.2.
 6) THE CONTROLS IN THE ACCESSIBLE ROLL-IN SHOWER WITH
 THE SEAT SHALL COMPLY WITH THE FAC SEC.608.5.2.
 7) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN ACCORDANCE
 WITH THE FAC SEC.608.6.
 8) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH
 THE FAC SEC. 610.3, 610.3.1.
 9) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER FAC SEC.609.4.
 10) SHT. A-12 - DETAIL #1 - SHOW THE INSIDE CLEAR
 DIMENSIONS (L X W) OF THE ACCESSIBLE TOILET ROOM.THE
 MINIMUM WIDTH SHALL BE 85 INCHES. 2014 FAC SEC. 604.3,
 606.
 11) SHT.A-13 - DETAIL #5 - THE THRESHOLD AT THE
 ACCESSIBLE SHOWER SHALL BE A 1/2 INCH MAXIMUM PER 2014
 FAC SEC.608.7.
 12) SHT. P1.1 - THE PRINTING ON THE PLAN FOR THE WATER
 AND SANITARY SIZES & NOTES IS SO SMALL IT IS ILLEGIBLE.
 SUBMIT A CLEAR AND LEGIBLE PLAN. FBC 107.2.1.
 13) SHT.P2.1 - DETAIL #10 SHOWS WATER HEATERS BUT IT IS
 LABELED AS "BACKFLOW PREVENTER ASSEMBLY."PLEASE
 CORRECT.
 14) SHT. P2.1 - THE WATER HEATERS ARE SHOWN AS GAS.
 SUBMIT A COMPLETE GAS DRAWING COMPLYING WITH THE
 FOLLOWING ITEMS:
  
 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER (IF
 APPLICABLE) OF THE CORRUGATED STAINLESS STEEL TUBING
 FOR EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3.) TYPE OF GAS (LP OR NATURAL).
  
 4.) BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413.
  
 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN
 THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6.) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426.
  
 9.) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 10.) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11.) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 15) THE BACKFLOW PREVENTION DEVICE SHALL BE LEAD FREE
 AND BE LISTED ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA"S (USC) LIST OF APPROVED DEVICES.
 16) A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW
 PREVENTION DEVICE.A SEPARATE PERMIT APPLICATION SHALL
 BE SUBMITTED WITH TWO COPIES OF THE SPECIFICATIONS FOR
 THE DEVICE.
 17) A CLEANOUT IS REQUIRED IN EACH WASTE OR SOIL STACK
 ( EXCEPT THE LAVATORY STACKS ) PER FPC SEC. 708.3.4.
 18) SHT. P3.1 - THE WATER CLOSETS IN THE MEN'S BATH #4
 & #5 ARE NOT VENTED. AS DRAWN, THEY ARE BEING WET
 VENTED AND CREATING A CODE VIOLATION OF SEC. 912.1 OF
 THE FPC FOR THE NUMBER AND TYPE OF FIXTURES ON THE WET
 VENT. INDIVIDUALLY VENTING THE TOILETS WILL SOLVE THIS
 PROBLEM.
 19) SHT.P3.1 - BATH #3 - A VENT IS REQUIRED BETWEEN THE
 WATER CLOSET AND THE SHOWER. 2014 FPC SEC.901.2 &
 901.2.1.
 20) SHT. P3.1 - THE 3 INCH VENT IN RESTROOM #9 IS SHOWN
 AS A FLAT, DRY VENT AND IS NOT PERMITTED. THE VENT
 SHALL CONNECT TO A HORIZONTAL DRAIN ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. FPC SEC.905.3.
 21) SHT. P3.1 - SIZE ALL VENTS ON THE SANITARY RISER.
 22) THE WASHING MACHINE SHALL BE INSTALLED ON A 3"
 STACK PER THE 2014 FPC SEC.406.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692