2016-03-16 14:57:36 | 1) SHT. A-2 - TOILET ROOM CALCULATIONS - THE TABLE |
| REFERENCED IS INCORRECT. THERE IS NO TABLE 400.1 IN THE |
| 2014 FLORIDA PLUMBING CODE. THE CORRECT TABLE IS 403.1. |
| PLEASE CORRECT. |
| 2) CLEARLY SHOW THE LOCATION OF THE REQUIRED SERVICE |
| SINKS FOR THE INSTITUTIONAL AND ASSEMBLY OCCUPANCIES AS |
| REQUIRED BY 2014 FPC TABLE 403.1. |
| 3) A MINIMUM OF ONE NEW WASHER AND ONE NEW DRYER IN THE |
| EXISTING LAUNDRY AREA SHALL COMPLY WITH THE 2014 FBC |
| ACCESS. SEC.611.1 - 611.4. |
| 4) SHT. A-11, DETAIL #2 - SHOW THE REQUIRED 30 INCH |
| WIDE MINIMUM BY 60 INCH LONG MINIMUM CLEAR FLOOR SPACE |
| ADJACENT TO THE OPEN FACE OF THE ACCESSIBLE SHOWER. |
| 5) GRAB BARS IN THE ACCESSIBLE ROLL-IN SHOWER WITH THE |
| SEAT SHALL BE LOCATE DIN ACCORDANCE WITH THE 2014 FAC |
| SEC.608.3.2. |
| 6) THE CONTROLS IN THE ACCESSIBLE ROLL-IN SHOWER WITH |
| THE SEAT SHALL COMPLY WITH THE FAC SEC.608.5.2. |
| 7) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN ACCORDANCE |
| WITH THE FAC SEC.608.6. |
| 8) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH |
| THE FAC SEC. 610.3, 610.3.1. |
| 9) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE PER FAC SEC.609.4. |
| 10) SHT. A-12 - DETAIL #1 - SHOW THE INSIDE CLEAR |
| DIMENSIONS (L X W) OF THE ACCESSIBLE TOILET ROOM.THE |
| MINIMUM WIDTH SHALL BE 85 INCHES. 2014 FAC SEC. 604.3, |
| 606. |
| 11) SHT.A-13 - DETAIL #5 - THE THRESHOLD AT THE |
| ACCESSIBLE SHOWER SHALL BE A 1/2 INCH MAXIMUM PER 2014 |
| FAC SEC.608.7. |
| 12) SHT. P1.1 - THE PRINTING ON THE PLAN FOR THE WATER |
| AND SANITARY SIZES & NOTES IS SO SMALL IT IS ILLEGIBLE. |
| SUBMIT A CLEAR AND LEGIBLE PLAN. FBC 107.2.1. |
| 13) SHT.P2.1 - DETAIL #10 SHOWS WATER HEATERS BUT IT IS |
| LABELED AS "BACKFLOW PREVENTER ASSEMBLY."PLEASE |
| CORRECT. |
| 14) SHT. P2.1 - THE WATER HEATERS ARE SHOWN AS GAS. |
| SUBMIT A COMPLETE GAS DRAWING COMPLYING WITH THE |
| FOLLOWING ITEMS: |
| |
| 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| G2413. |
| |
| 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER (IF |
| APPLICABLE) OF THE CORRUGATED STAINLESS STEEL TUBING |
| FOR EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 3.) TYPE OF GAS (LP OR NATURAL). |
| |
| 4.) BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2014 |
| FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4 |
| (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. |
| |
| 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN |
| THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| |
| 6.) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G |
| 2407. |
| |
| 7.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| SEC. G2413.2. . |
| |
| 8.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426. |
| |
| 9.) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. |
| |
| 10.) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF |
| THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| 11.) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS |
| ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF |
| REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE |
| ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, |
| THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170 |
| MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE. |
| |
| 15) THE BACKFLOW PREVENTION DEVICE SHALL BE LEAD FREE |
| AND BE LISTED ON THE UNIVERSITY OF SOUTHERN |
| CALIFORNIA"S (USC) LIST OF APPROVED DEVICES. |
| 16) A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW |
| PREVENTION DEVICE.A SEPARATE PERMIT APPLICATION SHALL |
| BE SUBMITTED WITH TWO COPIES OF THE SPECIFICATIONS FOR |
| THE DEVICE. |
| 17) A CLEANOUT IS REQUIRED IN EACH WASTE OR SOIL STACK |
| ( EXCEPT THE LAVATORY STACKS ) PER FPC SEC. 708.3.4. |
| 18) SHT. P3.1 - THE WATER CLOSETS IN THE MEN'S BATH #4 |
| & #5 ARE NOT VENTED. AS DRAWN, THEY ARE BEING WET |
| VENTED AND CREATING A CODE VIOLATION OF SEC. 912.1 OF |
| THE FPC FOR THE NUMBER AND TYPE OF FIXTURES ON THE WET |
| VENT. INDIVIDUALLY VENTING THE TOILETS WILL SOLVE THIS |
| PROBLEM. |
| 19) SHT.P3.1 - BATH #3 - A VENT IS REQUIRED BETWEEN THE |
| WATER CLOSET AND THE SHOWER. 2014 FPC SEC.901.2 & |
| 901.2.1. |
| 20) SHT. P3.1 - THE 3 INCH VENT IN RESTROOM #9 IS SHOWN |
| AS A FLAT, DRY VENT AND IS NOT PERMITTED. THE VENT |
| SHALL CONNECT TO A HORIZONTAL DRAIN ABOVE THE |
| CENTERLINE OF THE HORIZONTAL DRAIN PIPE. FPC SEC.905.3. |
| 21) SHT. P3.1 - SIZE ALL VENTS ON THE SANITARY RISER. |
| 22) THE WASHING MACHINE SHALL BE INSTALLED ON A 3" |
| STACK PER THE 2014 FPC SEC.406.2. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |