2016-03-17 08:46:251ST REVIEW:
 CODES: FBC 2014 MECHANICAL, EXISTING BUILDING, ENERGY
 CONSERVATION
 PERMIT #16030222
 3/17/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS
 AND SPACES IN ACCORDANCE WITH TABLE 403.3 MECHANICAL.
 PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE
 REQUIRED AND PROVIDED CFM'S OF O/A.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR
 RTU-9 IN ACCORDANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 3) THE PROPOSED PROJECT IS CLASSIFIED AS A "RENOVATION"
 IN ACCORDANCE WITH SECTION 202 FBC-14 ENERGY
 CONSERVATION, AND THEREFORE REQUIRES DOCUMENTATION OF
 ENERGY EFFICIENCY COMPLIANCE- SEE SECTIONS C101.4.3,
 C101.5.1, AND C401.2. PLEASE SHOW COMPLIANCE USING
 EITHER THE PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE
 PATHS.
  
 4) PROVIDE MOTORIZED DAMPERS FOR MTHE O/A TO EACH RTU
 THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS AND
 SPACES ARE NOT IN USE.
  
 5) REFER TO SECTION C403.2.5.1 AND PROVIDE DEMAND
 CONTROLLED VENTILATION IN ROOMS AND SPACES WHERE
 APPLICABLE.
  
 6) PROVIDE A DUCT SMOKE DETECTOR SYMBOL AT THE RETURN
 AIR PLENUM, OF RTU-9 AND ALL OTHER SYSTEMS REQUIRING
 DETECTORS- SECTION 606.2.1. PLEASE INDICATE A SEQUENCE
 OF OPERATION FOR THE DETECTORS- CLARIFY IF ALL SYSTEMS
 WILL BE LINKED TOGETHER TO SHUT DOWN UPON
 ACTIVATIVATION OF ANY ONE DETECTOR.
  
 7) PROVIDE WIND LOAD ENGINEERING FOR TIE-DOWN OF THE
 NEW RTU-9 IN ACCORDANCE WITH SECTION 301.15 FBC-14
 MECHANICAL. PROVIDE THE WIND LOAD DESIGN CRITERIA ON
 THE PLAN AND SECTION CUTS OF THE UNIT AND CURB SHOWING
 THE STRUCTURAL DETAILS- PLEASE NOTE THAT THE DETAIL ON
 M2.1 IS INCOMPLETE.
  
 8) PROVIDE A ROOF PLAN SHOWING THE LOCATION OF THE NEW
 RTU-9 AND CLEARANCE DISTANCE MEASUREMENTS FROM THE AIR
 INTAKE TO MECHANICAL AND GRAVITY EXHAUST OUTLETS, AND
 FROM THE RTU TO THE ROOF EDGES.
  
 9) PROVIDE A CONDENSATE DISPOSAL FOR THE RTU-9
 INDICATING PIPING DETAILS AND DISCHARGE LOCATION.
 PLEASE NOTE THAT NO DETAILS ARE SHOWN ON THE PLUMBING
 PAGES.
  
 10) PROVIDE THE MAIN DUCT SIZES ON THE PLANS FOR RTU-4,
 AND SEE SECTION 601.5: PLEASE NOTE THE 10" TRANSFER MAY
 BE UNDERSIZED.
  
 11) PLEASE CLARIFY IF THE TOILOET ROOM EXHAUST FANS AND
 DUCTS ARE BEING REPLACED AND PROVIDE DETAILS AND
 EQUIPMENT SCHEDULES IF APPLICABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719