Plan Review Notes For Permit 16030222 |
Permit Number |
16030222 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-11 11:56:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. SHEET A 5 - THE EXIT SEPARATION DISTANCE DOES NOT | | APPEAR TO COMPLY WTH NFPA 101, CHAPTER 7, MEANS OF | | EGRESS, PER NFPA 101, CHAPTER 7, 7.5.1.3.2, WHERE TWO | | EXITS, EXIT ACCESSES, OR EXIT DISCHARGES ARE REQUIRED, | | THEY SHALL BE LOCATED AT A DISTANCE FROM ONE ANOTHER | | NOT LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM | | OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA TO | | BE SERVED, MEASURED IN A STRAIGHT LINE BETWEEN THE | | NEAREST EDGE OF THE EXITS, EXIT ACCESSES, OR EXIT | | DISCHARGES. | | | | PLEASE PROVIDE COMPLIANCE WITH THIS REQUIRMENT. | | | | 2. SHEET A 4, A 9, A 14 - ALL DOOR HARWARE AND LOCKS IN | | THE EXIT PATH OF TRAVEL SHALL COMPLY WITH NFPA 101, | | CHAPTER 7 MEANS OF EGRESS, | | | | D61 - NO EXIT DOOR HARDWARE INDICATED | | | | D10 - NO EXIT DOOR HARDWARE INDICATED | | | | D 38 - NO EXIT DOOR HARDWARE INDICATED | | | | D 9 - NO EXIT DOOR HARDWARE INDICATED, NO FIRE RATING | | INDICATED. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|