2016-03-14 08:43:12INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ADD A NOTE TO INDICATE NEC 110.16 ARC-FLASH WARNING
 LABELS REQUIRED. A NOTE WILL SUFFICE.
 2. ON SHEET E1.1 UPDATE ELECTRICAL NOTES TO INDICATE
 NEC 2011 NOT 2005 CODE EDITION.
 3. PROVIDE A NOTE TO INDICATE SEPARATE PERMITS REQUIRED
 FOR ANY LOW VOLTAGE SYSTEMS
 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  