Plan Review Notes For Permit 16030222 |
Permit Number |
16030222 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-14 08:43:12 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. ADD A NOTE TO INDICATE NEC 110.16 ARC-FLASH WARNING | | LABELS REQUIRED. A NOTE WILL SUFFICE. | | 2. ON SHEET E1.1 UPDATE ELECTRICAL NOTES TO INDICATE | | NEC 2011 NOT 2005 CODE EDITION. | | 3. PROVIDE A NOTE TO INDICATE SEPARATE PERMITS REQUIRED | | FOR ANY LOW VOLTAGE SYSTEMS | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | ANY QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|