Plan Review Notes
Plan Review Notes For Permit 16030222
Permit Number 16030222
Review Stop B
Sequence Number 1
Notes
Date Text
2016-03-21 06:40:40BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030222
 ADD: 5400 EAST AVENUE
 CONT: STUART & SHELBY DEVELOPMENT
 TEL: 561-637-7902
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 18/ 2016
 ACTION: DENIED
  
 1) SHEET A9 INDICATES THE WINDOW AND EXTERIOR DOOR
 POSITIVE & NEGATIVE PRESSURES. PLEASE PROVIDE WHERE THE
 WIND DESIGN CRITERIA CAN BE LOCATED IN THE PLANS.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2.
 ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2).
  
 2) SHEET A7 SHOWS A WHITE BAHAMA STYLE SHUTTER, PLEASE
 PROVIDE IF THIS RIGID AWNING WILL STAY AS POSITIONED OR
 REPOSITIONED TO CLOSE AN OPENING WHEN THE BUILDING IS
 UNATTENDED OR ACT AS A STORM SHUTTER, THE DESIGN IN THE
 CLOSED POSITION SHALL ALSO COMPLY WITH CHAPTER 16 AND
 SHALL BE IMPACT RESISTANT IN ACCORDANCE WITH SECTION
 1609.1.2 FBC-B.
  
 3) SHEET A7 & 8 BOTH SHOW DETAILS OF CULTURED STONE
 VENEER 2008 MIST DRYSTACK LEDGESTONE OWENS CORNING.
 PLEASE SUBMIT THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. THE PLANS DO NOT INDICATE IF THE STONE IS
 ATTACHED OR ADHERED. PLEASE PROVIDE COMPLIANCE WITH ONE
 OF THESE CODE SECTIONS:
 2014 FBC-B 1405.6. ANCHORED MASONRY VENEERS
 1405.7 STONE VENEERS
 1405.10 ADHERED MASONRY VENEERS
 1405.10.2 EXTERIOR ADHERED MASONRY VENEERS/ PORCELAIN
 TILE.
  
 4) PLEASE NOTE THIS PROPERTY IS LOCATED WITHIN AN AH
 FLOOD ZONE. FBC BUILDING 1612 AND CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED. PLEASE REVIEW CITY ORDINANCE FOR THE CITY
 REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF
 ELEVATION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) SHEET M1.1 SHOWS A NEW ROOF TOP RTU # 9 PLEASE
 PROVIDE ENGINEERING FOR THE FRAMING AROUND THE NEW ROOF
 TOP HOLE FOR THIS UNIT. ALSO PROVIDE THE MANUFACTURERS
 INSTALLATION INSTRUCTIONS, IF A PRODUCT APPROVAL PLEASE
 PROVIDE AS WELL AS THE TIE DOWN OF THE RTU TO THE CURB.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES/ CURBS/ ROOF TOP
 FANS
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 6) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) IF ZONING REQUIRES A MECHANICAL EQUIPMENT SCREEN FOR
 THE NEW ROOF TOP EQUIPMENT THEN SHOW COMPLIANCE WITH:
 FBC-B 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 SHEET A4 SHOWS NEW TRAY SLIDES BY OTHERS, PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE:
  
 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  