Plan Review Notes
Plan Review Notes For Permit 16030214
Permit Number 16030214
Review Stop G
Sequence Number 1
Notes
Date Text
2016-03-05 04:58:541) THE MAXIMUM BTU LOAD ON THE CSST IS 62K PER TABLE
 402.4 (15).. THE LINE HAS TO BE SIZED BASED ON THE
 TOTAL DISTANCE OF 100 FEET FROM THE SOURCE OF DELIVERY.
 THE 3/4" LINE IS UNDERSIZED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR