Plan Review Notes For Permit 16030214 |
Permit Number |
16030214 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-05 04:58:54 | 1) THE MAXIMUM BTU LOAD ON THE CSST IS 62K PER TABLE | | 402.4 (15).. THE LINE HAS TO BE SIZED BASED ON THE | | TOTAL DISTANCE OF 100 FEET FROM THE SOURCE OF DELIVERY. | | THE 3/4" LINE IS UNDERSIZED. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|