2016-03-09 03:30:511) THE MAXIMUM ALLOWABLE BTU LOAD ON 3/4" CSST AT A
 TOTAL DEVELOPED LENGTH OF 100 FT. IS 62,000 BTU'S. THE
 RANGE HAS A BTU VALUE OF 65,000. THE MINIMUM SIZE LINE
 SHALL BE 1" ( EHD 30) PER 2014 FGC TABLE 402.4 (15).
  