Plan Review Notes For Permit 16030212 |
Permit Number |
16030212 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-09 03:30:51 | 1) THE MAXIMUM ALLOWABLE BTU LOAD ON 3/4" CSST AT A | | TOTAL DEVELOPED LENGTH OF 100 FT. IS 62,000 BTU'S. THE | | RANGE HAS A BTU VALUE OF 65,000. THE MINIMUM SIZE LINE | | SHALL BE 1" ( EHD 30) PER 2014 FGC TABLE 402.4 (15). | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|