Plan Review Notes
Plan Review Notes For Permit 16030207
Permit Number 16030207
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-03-09 12:08:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THERE IS AN INCORRECT REFERENCE TO THE FIRE CODE:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 THIS DOES NOT APPEAR TO NEGATIVELY AFFECT YOUR
 SUBMITTAL; HOWEVER, YOU ARE ENCORAGED TO HAVE YOUR
 DESIGNERS/CONTRACTORS REVIEW TO ENSURE COMPLIANCE WITH
 THE CORRECT CODE.
  
 PLEASE UPADATE YOU RECORDS FOR FUTURE SUBMITTALS.
  
 CONTINUED USE OF THE INCORRECT CODE WILL RESULTED IN A
 FAILED REVIEW.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  