2016-03-31 15:20:17PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE INFORMATION THAT YOU SUBMITTED FOR THE SIMPSON
 A33 CONNECTORS SPECIFY THE ALLOWABLE LATERAL LOADS (F1
 AND F2). NO ALLOWABLE UPLIFT LOADS ARE LISTED. THE
 FASTENERS THAT WERE SPECIFIED ON THE PLANS ARE NOT THE
 SAME AS THE ONES LISTED IN THE SIMPSON CATALOG PAGE
 THAT YOU SUBMITTED. REVISE THE DRAWINGS AND SUBMIT
 PRODUCT APPROVALS FOR CONNECTORS WITH ALLOWABLE UPLIFT
 LOADS. DCA RULE 9N-3, R301.1 & R802.2
  
 2) FBC R301.1 INDICATE WHICH ONE OF THE THREE EMBED
 DEPTHS LISTED FOR TECTUM DECKS IN THE TRUFAST CHART ON
 THE FASTENER SHEET THAT WAS SUBMITTED IS TO BE USED.
 BASED ON THE DRAWINGS THERE IS ONE FASTENER FOR EVERY
 FOUR SQUARE FEET OF ROOF AREA. FOR EXAMPLE THE FASTENER
 WITH THE 2.5" EMBEDMENT IS 595 LBS. DIVIDED BY 4 SQUARE
 FEET = 148.45 POUNDS PER SQUARE FOOT. THE PLANS STATE
 THAT THE WORST CASE IS -111 PSF.
  
  