2016-03-07 09:05:07PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS THE CONSTRUCTION OF A NEW ROOF
 SYSTEM BUILT OVER AN EXISTING ROOF. THE ROOF FRAMING
 AND SHEATHING PORTION OF THIS PROPOSED WORK WILL
 REQUIRE A FLORIDA LICENSED GENERAL, BUILDING OR
 RESIDENTIAL CONTRACTOR. FS489
  
 2) SUBMIT PRODUCT APPROVALS FOR THE SIMPSON A33
 CONNECTORS THAT INDICATE THE ALLOWABLE UPLIFT LOADS.
 THESE ANGLE CLIPS DO NOT APPEAR TO BE SUITABLE FOR
 UPLIFT APPLICATIONS. DCA RULE 9N-3, R301.1 & R802.2
  
 3) PROVIDE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS
 FOR THE TRUFAST TECTUM FASTENERS THAT WILL BE USED TO
 ATTACH THE 2" X 4" P.T. SLEEPERS TO THE EXISTING TECTUM
 DECK. FBC R301.1
  
 4) SPECIFY THE REQUIRED EMBED DEPTH AND THE PULL OUT
 VALUE FOR THE TRUFAST TECTUM FASTENERS. FBC R301.1
  
 5) SPECIFY THE REQUIRED UPLIFT OF THE NEW ROOF FRAMING
 SYSTEM AND PROVIDE CALCULATIONS TO SHOW THAT THE
 PROPOSED CONNECTORS ARE ADEQUATE TO PROVIDE A COMPLETE
 LOAD PATH. FBCR 301.1 & FBC 107.2.1.3