Plan Review Notes For Permit 16030202 |
Permit Number |
16030202 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-07 09:05:07 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THIS PROJECT IS THE CONSTRUCTION OF A NEW ROOF | | SYSTEM BUILT OVER AN EXISTING ROOF. THE ROOF FRAMING | | AND SHEATHING PORTION OF THIS PROPOSED WORK WILL | | REQUIRE A FLORIDA LICENSED GENERAL, BUILDING OR | | RESIDENTIAL CONTRACTOR. FS489 | | | | 2) SUBMIT PRODUCT APPROVALS FOR THE SIMPSON A33 | | CONNECTORS THAT INDICATE THE ALLOWABLE UPLIFT LOADS. | | THESE ANGLE CLIPS DO NOT APPEAR TO BE SUITABLE FOR | | UPLIFT APPLICATIONS. DCA RULE 9N-3, R301.1 & R802.2 | | | | 3) PROVIDE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS | | FOR THE TRUFAST TECTUM FASTENERS THAT WILL BE USED TO | | ATTACH THE 2" X 4" P.T. SLEEPERS TO THE EXISTING TECTUM | | DECK. FBC R301.1 | | | | 4) SPECIFY THE REQUIRED EMBED DEPTH AND THE PULL OUT | | VALUE FOR THE TRUFAST TECTUM FASTENERS. FBC R301.1 | | | | 5) SPECIFY THE REQUIRED UPLIFT OF THE NEW ROOF FRAMING | | SYSTEM AND PROVIDE CALCULATIONS TO SHOW THAT THE | | PROPOSED CONNECTORS ARE ADEQUATE TO PROVIDE A COMPLETE | | LOAD PATH. FBCR 301.1 & FBC 107.2.1.3 |
|