2016-03-14 18:00:19 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PLAN SHEETS A-2 AND A-3 CONTAIN STRUCTURAL | | INFORMATION AND HAVE THE ENGINEER'S INFORMATION. THESE | | SHEETS REQUIRE THE ENGINEER'S SEAL AND ORIGINAL | | HANDWRITTEN SIGNATURE. | | | | 2) PLAN SHEETS A-1, A-2 AND S-1 INCORRECTLY REFERS TO | | THE 2015 FBC AND THE 2014 FBC IS THE ONE THAT APPLIES. | | PLEASE CORRECT. | | | | 3) THE ROOF REVISION NOTES ON SHEETS A-2 AND A-3 ARE | | ILLEGIBLE. FBC 107.2.1 | | | | 4) ON SHEET S-1, THE LINTEL SIZE FOR THE ADDED FRENCH | | DOOR WAS NOT CHANGED ON THE SECOND FLOOR FRAMING PLAN | | OR IN THE LINTEL TABLE. FBC 107.2.1 |
|