Plan Review Notes For Permit 16030156
Permit Number 16030156
Review Stop M
Sequence Number 2
Notes
Date Text
2016-04-11 17:47:31FLORIDA BUILDING CODE RESIDENTIAL (5TH EDITION) 2014
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 107.2.1 - PROVIDE INSTALLATION INSTRUCTIONS FOR
 CONDENSER TIE DOWNS. AS PER FBC 2014 WINDLOAD
 REQUIREMENTS (170 MPH).
  