2016-03-24 17:45:50FLORIDA ENERGY CODE - SECTION R101.4.3 - SECTION R202
 RENOVATED BUILDINGS - A RESIDENTIAL OR NONRESIDENTIAL
 BUILDING UNDERGOING ALTERATION THAT VARIES INSULATION,
 HVAC SYSTEMS, WATER HEATING SYSTEMS, OR EXTERIOR
 ENVELOPE CONDITIONS, PROVIDED THE ESTIMATED COST OF
 RENOVATION EXCEEDS 30 PERCENT OF THE ASSESSED VALUE OF
 THE STRUCTURE.
  
 PROVIDE ENERGY CALCULATIONS.
  
 107.2.1 - PROVIDE DUCT SIZES AND CFM QUANTITIES FOR ALL
 BATHROOM EXHAUST, DRYER EXHAUST AND KITCHEN EXHAUST.
 PROVIDE CONDENSER TIE DOWN SCHEDULE. PROVIDE KITCHEN
 EXHAUST EQUIPMENT SPECIFICATIONS.
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY
 EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY
 IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT
 MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD
 CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN
 SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED
 BY THE MANUFACTURER?S PRODUCT LINES. THE CORRESPONDING
 LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN
 THE CALCULATED LATENT LOAD.
  
 AS PER THE SUBMITTED MECHANICAL PLANS, THE COOLING BTU
 EXCEED THE RESIDENTIAL HVAC LOAD CALCULATIONS BY MORE
 THAN 1.15 TIMES. CONFIRM AND MAKE CORRECTIONS.
  