Plan Review Notes
Plan Review Notes For Permit 16030116
Permit Number 16030116
Review Stop P
Sequence Number 1
Notes
Date Text
2016-03-03 13:18:211) THE SUBMITTED PLAN IS UNCLEAR AS TO THE SCOPE OF
 WORK TO BE DONE.WILL THERE BE ANY TUNNELING REQUIRED
 UNDER THE EXISTING SLAB? INDICATE ON THE PLANS.
 2) PLUMBING REPAIR TUNNEL WORK
 A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE
 SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO
 EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED,
 THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO
 EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS.
 DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED
 THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE
 CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND
 BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED FOR
 BACKFILL BELOW GROUND PER THE FLORIDA BUILDING CODE,
 RESIDENTIAL, SECTION 318.8 AND THE FLORIDA BUILDING
 CODE, BUILDING, SECTION 2603.9.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR