Plan Review Notes For Permit 16030102 |
Permit Number |
16030102 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-04-21 17:35:59 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | PASSED WITH A PROVISO : | | | | NEC 408.4 B DIRECTORY SHOWING SOURCE OF SUPPLY FOR THE | | SUB PANELS . | | NEC 225.37 IDENTIFICATION OF THE SERVICE DISCONECTING | | MEANS. | | NEC 230.2 E A PERMANT PLAQUE DISPLAYING ALL SERVICE | | LOCATIONS. |
|