2016-04-15 07:47:33 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16030102 |
| W. P. B. PERMIT: 15090236 |
| ADD:2087 PALM BEACH LAKES |
| CONT: LM DEVELOPMENT GROUP |
| TEL: ( 954)476-0800 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: FRI. APRIL 15/2016 |
| ACTION: DENIED |
| |
| 1) NOTICE ONLY, NO ACTION NEEDED AT THIS TIME. REVISION |
| INCREASE WENT FROM $10,000 TO $95,000.00 FOR THE |
| MECHANICAL, ELECTRICAL & PLUMBING BEING ADDED TO THE |
| BASE BUILDING PERMIT. NOTE VALUES GO ON THE BASE |
| BUILDING PERMIT. SUB-PERMITS COME IN AS A $80.00 COST |
| FOR ADMINISTRATIVE SERVICES, NO VALUE. |
| |
| 2) SEMI-COMPLIED . REVISION SHEET S-4 PROVIDES THE |
| ANCHOR DETAILS FOR THE CURB TO THE DECK AND THE ROOF |
| TOP UNIT TO THE CURB. WE ARE STILL MISSING THE APPROVAL |
| FOR THE CURB. THE CONTRACTOR IS TO SUBMIT THE CURB |
| APPROVAL TO THE DESIGNER OF RECORD FOR REVIEW, IF |
| APPROVED THEN THE DESIGNER OF RECORD IS TO APPLY THEIR |
| SHOP DRAWING STAMP OF APPROVAL ON THE DOCUMENT BEFORE |
| SUBMITTAL TO THE BUILDING DEPARTMENT. THE M1 SHEET |
| SHOWS 5 NEW ROOF TOP A/C UNITS A REVISION TO THE |
| ORIGINAL PERMIT. |
| |
| PLEASE PROVIDE THE ACTUAL ROUGH OPENING SIZE FOR THE |
| ROOF PENETRATIONS. NOTE ON THE S-4 SHEET INDICATES |
| COORDINATE THE EXACT SIZE OF HOLE AND REQUIREMENTS WITH |
| MECHANICAL CONTRACTOR. THE SUBMITTAL FOR THE CURB SIZE |
| IS UNKNOWN, NOT PROVIDED, HOW CAN THE STRUCTURAL CALCS |
| BE ACCURATE? |
| |
| PLEASE NOTE THE SEA COAST ENGINEERING SUBMITTAL FOR THE |
| MODEL/ TAG THC092 IS 2 TONS LARGER THAN SPECED IN ON |
| M-1. PLEASE REVIEW SHEET M-1 RTU SPECIFICATIONS, UNIT |
| SPECED IN IS A TSC072. |
| |
| 2A) 2ND REQUEST UNTIL THE UNKNOWNS ABOVE ARE SATISFIED |
| THE AND DISCREPANCIES CLEARED UP THE WIND LOAD |
| CERTIFICATION CANNOT BE APPROVED. |
| DISCREPANCIES!!!!!!2014 FBC-B 1604.4 ANALYSIS. LOAD |
| EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS |
| SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS |
| THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, |
| GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM |
| MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| WIND LOADS? |
| |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2B) SEMI-COMPLIED, DISCREPANCIES , AND UNKNOWN |
| DIMENSION IN OPENINGS. |
| IF THE ABOVE MENTIONED IS DESIGNED BY EITHER A DELEGATE |
| ENGINEER OR MECHANICAL ENGINEER THE ENGINEER OF RECORD |
| WILL NEED TO REVIEW THE ENGINEERED DETAILS FOR |
| CONFORMANCE WITH THEIR OVERALL DESIGN FOR THE BUILDING. |
| 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| ENGINEERING SUBMITTED FORM BOEDOIN HUTCHINSON A |
| DELEGATE ENGINEER WILL NEED TO BE SUBMITTED TO STEPHEN |
| H. PAGE THE ENGINEER OF RECORD, ALSO NOTE THE SUBMITTED |
| CALCULATIONS ARE COPIES NOT SIGNED AND SEALED |
| ORIGINALS. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| 3 SETS OF PLANS SUBMITTED ONLY (2) SETS OF COPIES |
| SUBMITTED NOT (3) ORIGINALS. |
| |
| 3) UNTIL THE DISCREPANCIES IN THE ROOF TOP RTU?S IS |
| SATISFIED THIS COMMENT WILL STAND. THIS BUILDING WAS |
| DESIGNED AS A SHELL BUILDING EXEMPT FROM THE ENERGY |
| CODE. WITH THE A/C ROOF TOP UNITS BEING ADDED TO THE |
| SCOPE OF WORK, ELECTRICAL AND PLUMBING FOR THE HOOK UP |
| OF THESE UNITS THE BUILDING NO LONGER QUALIFIES AS A |
| SHELL BUILDING AND WILL NEED TO MEET THE REQUIREMENTS |
| FOUND UNDER THE 2014 FBC-ENERGY CODE; |
| 3A) C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL |
| COMPLY WITH ONE OF THE FOLLOWING: |
| 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| WITH EITHER SECTION C406.2, C406.3 OR |
| C406.4. |
| 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| BUILDING ENERGY COST SHALL BE EQUAL |
| TO OR LESS THAN 85 PERCENT OF THE STANDARD REFERENCE |
| DESIGN BUILDING. |
| |
| NOTE ASHRAE 90 CALCS. WERE SUBMITTED BUT THE MANDATORY |
| REQUIREMENTS FOUND ON PAGE 8 OF 13 NOT COMPLETED. TO BE |
| CHECKED AT COMPLIANCE SUBMISSION, ALL BOXES WERE LEFT |
| BLANK!!!!!! |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |