2016-03-08 09:48:52PLAN DENIED
  
 1) VALUE IS TO LOW
 2) OUT DOOR AIR REQUIRED ON PLAN.
 PER TABLE 403.3 FBC (M) 2014
 3) DETAIL FROM THE ENGINEER ON CURB TO ROOF TIEDOWN
 AND RTU TO CURB TIEDOWN. PER SECTION 301.15
 WIND RESISTANCE 2014 FBC (M)
  