2016-03-09 19:16:18 | JOB PERMIT NUMBER: 16030102 |
| JOB ADDRESS: 2087 PALM BEACH LAKES BLVD |
| WEST PALM BEACH FLORIDA |
| DATE: MARCH 9 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY |
| WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| SEALING MATERIALS. |
| - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, |
| SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE |
| SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE |
| LOCATED WITHIN 25 FT. OF THE EQUIPMENT. ( RTU 4 & 5 |
| WITHIN SIGHT. ) |
| - NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| 15 AND 20 AMPERE, 125 AND 250 VOLT NON-LOCKING |
| RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| ?WR?. |
| - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| CONSIDERED ACCESSIBLE TO PEDESTRIANS. |
| - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| EQUIPMENT, SWITCHBOARDS, PANELBOARDS. |
| - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| INSTALLED. |
| - FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER OWNED |
| SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2% |
| VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR A |
| MAXIMUM OF 3% VOLTAGE DROP. |
| - PLEASE CLARIFY CONDUIT DETAILS BY PROVIDING A FEEDER |
| SCHEDULE SHOWING RACEWAY FILL SPECS. |
| - PLEASE PROVIDE GUARDING TO SERVICE EQUIPMENT AND |
| INTERIOR PANELS. NEC 110.27 , 110.12 IF SUBJECT TO |
| ACCIDENTAL CONTACT. FURTHERMORE IDENTIFY SUB PANEL FOR |
| ADDRESS 2089 AND 2087 ? |
| - EMERGENCY LIGHTING IS REQUIRED AS MINIMUM FOR SHELL |
| BUILD OUT. FBC-B 1006.2. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |