2016-03-11 07:34:02 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16030102 |
| W. P. B. PERMIT: 15090236 |
| ADD:2101 PALM BEACH LAKES (744343190020900) |
| CONT: LM DEVELOPMENT GROUP |
| TEL: ( 954)476-0800 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: FRI. MARCH 11/2016 |
| ACTION: DENIED |
| |
| 1) THE CONTRACTOR HAS INCREASED THE SCOPE OF WORK FROM |
| JUST A SHELL BUILDING WITH THE ADDITIONAL WORK INCLUDED |
| MECHANICAL, PLUMBING AND ELECTRICAL. |
| THE VALUE OF THE INCREASE IN THE SCOPE OF WORK IS |
| DECLARED AS $10,000.00 DOLLORS. SHEET M1 SHOWS 5 ROOF |
| TOP A/C UNITS ALONE, NOT COUNTING THE ADDITIONAL |
| ELECTRICAL AND PLUMBING WORK AS WELL AS THE BUILDING |
| CONTRACTORS WORK. |
| |
| W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) THE M1 SHEET SHOWS 5 NEW ROOF TOP A/C UNITS A |
| REVISION TO THE ORIGINAL PERMIT. ON THE SHELL BUILDING |
| SHEET S-4 SHOWED THE TYPICAL ROOF OPENING FRAMING |
| DETAIL, BUT THERE ARE NO CURB DETAILS OF HOW THE CURB |
| WILL BE ANCHORED, NOR IS THERE DETAILS OF HOW THE A/C |
| UNIT WAS TO BE ANCHORED TO THE CURB. |
| PLEASE PROVIDE DETAILS SHOWING CODE COMPLIANCE WITH: |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31) (D) ROOFING PRODUCTS AND ASSEMBLIES ROOF TOP |
| CURBS. |
| |
| 2A) 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2B) IF THE ABOVE MENTIONED IS DESIGNED BY EITHER A |
| DELEGATE ENGINEER OR MECHANICAL ENGINEER THE ENGINEER |
| OF RECORD WILL NEED TO REVIEW THE ENGINEERED DETAILS |
| FOR CONFORMANCE WITH THEIR OVERALL DEDIGN FOR THE |
| BUILDING. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED |
| BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| ENGINEERING SUBMITTED FORM BOEDOIN HUTCHINSON A |
| DELEGATE ENGINEER WILL NEED TO BE SUBMITTED TO STEPHEN |
| H. PAGE THE ENGINEER OF RECORD, ALSO NOTE THE SUBMITTED |
| CALCULATIONS ARE COPIES NOT SIGNED AND SEALED |
| ORIGINALS. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| 3 SETS OF PLANS SUBMITTED ONLY (2) SETS OF COPIES |
| SUBMITTED NOT (3) ORIGINALS. |
| |
| 3) THIS BUILDING WAS DESIGNED AS A SHELL BUILDING |
| EXEMPT FROM THE ENERGY CODE. WITH THE A/C ROOF TOP |
| UNITS BEING ADDED TO THE SCOPE OF WORK, ELECTRICAL AND |
| PLUMBING FOR THE HOOK UP OF THESE UNITS THE BUILDING NO |
| LONGER QAULIFIES AS A SHELL BUILDING AND WILL NEED TO |
| MEET THE REQUIREMENTS FOUND UNDER THE 2014 FBC-ENERGY |
| CODE; |
| 3A) C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL |
| COMPLY WITH ONE OF THE FOLLOWING: |
| 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| WITH EITHER SECTION C406.2, C406.3 OR |
| C406.4. |
| 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| BUILDING ENERGY COST SHALL BE EQUAL |
| TO OR LESS THAN 85 PERCENT OF THE STANDARD REFERENCE |
| DESIGN BUILDING. |
| |
| NOTE ASHRAE 90 CALCS WERE SUBMITTEDBUTTHE MANDATORY |
| REQUIREMENTS FOUND ON PAGE 8 OF 13 NOT COMPLETED. TO |
| BECHECKED AT COMPLIANCE SUBMISSION, ALL BOXES WERE LEFT |
| BLANK!!!!!! |
| |
| 3B) NO LOAD CALS SUBMITTED.!!!!!!!! C403.2.1 |
| CALCULATION OF HEATING AND COOLING LOADS. SUBMIT 3 SETS |
| OF CALCS. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |