2016-03-11 07:34:02BUILDING PLAN REVIEW
 W. P. B. REVISION: 16030102
 W. P. B. PERMIT: 15090236
 ADD:2101 PALM BEACH LAKES (744343190020900)
 CONT: LM DEVELOPMENT GROUP
 TEL: ( 954)476-0800
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. MARCH 11/2016
 ACTION: DENIED
  
 1) THE CONTRACTOR HAS INCREASED THE SCOPE OF WORK FROM
 JUST A SHELL BUILDING WITH THE ADDITIONAL WORK INCLUDED
 MECHANICAL, PLUMBING AND ELECTRICAL.
 THE VALUE OF THE INCREASE IN THE SCOPE OF WORK IS
 DECLARED AS $10,000.00 DOLLORS. SHEET M1 SHOWS 5 ROOF
 TOP A/C UNITS ALONE, NOT COUNTING THE ADDITIONAL
 ELECTRICAL AND PLUMBING WORK AS WELL AS THE BUILDING
 CONTRACTORS WORK.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE M1 SHEET SHOWS 5 NEW ROOF TOP A/C UNITS A
 REVISION TO THE ORIGINAL PERMIT. ON THE SHELL BUILDING
 SHEET S-4 SHOWED THE TYPICAL ROOF OPENING FRAMING
 DETAIL, BUT THERE ARE NO CURB DETAILS OF HOW THE CURB
 WILL BE ANCHORED, NOR IS THERE DETAILS OF HOW THE A/C
 UNIT WAS TO BE ANCHORED TO THE CURB.
 PLEASE PROVIDE DETAILS SHOWING CODE COMPLIANCE WITH:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES ROOF TOP
 CURBS.
  
 2A) 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2B) IF THE ABOVE MENTIONED IS DESIGNED BY EITHER A
 DELEGATE ENGINEER OR MECHANICAL ENGINEER THE ENGINEER
 OF RECORD WILL NEED TO REVIEW THE ENGINEERED DETAILS
 FOR CONFORMANCE WITH THEIR OVERALL DEDIGN FOR THE
 BUILDING. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ENGINEERING SUBMITTED FORM BOEDOIN HUTCHINSON A
 DELEGATE ENGINEER WILL NEED TO BE SUBMITTED TO STEPHEN
 H. PAGE THE ENGINEER OF RECORD, ALSO NOTE THE SUBMITTED
 CALCULATIONS ARE COPIES NOT SIGNED AND SEALED
 ORIGINALS. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 3 SETS OF PLANS SUBMITTED ONLY (2) SETS OF COPIES
 SUBMITTED NOT (3) ORIGINALS.
  
 3) THIS BUILDING WAS DESIGNED AS A SHELL BUILDING
 EXEMPT FROM THE ENERGY CODE. WITH THE A/C ROOF TOP
 UNITS BEING ADDED TO THE SCOPE OF WORK, ELECTRICAL AND
 PLUMBING FOR THE HOOK UP OF THESE UNITS THE BUILDING NO
 LONGER QAULIFIES AS A SHELL BUILDING AND WILL NEED TO
 MEET THE REQUIREMENTS FOUND UNDER THE 2014 FBC-ENERGY
 CODE;
 3A) C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR
 C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL
 TO OR LESS THAN 85 PERCENT OF THE STANDARD REFERENCE
 DESIGN BUILDING.
  
 NOTE ASHRAE 90 CALCS WERE SUBMITTEDBUTTHE MANDATORY
 REQUIREMENTS FOUND ON PAGE 8 OF 13 NOT COMPLETED. TO
 BECHECKED AT COMPLIANCE SUBMISSION, ALL BOXES WERE LEFT
 BLANK!!!!!!
  
 3B) NO LOAD CALS SUBMITTED.!!!!!!!! C403.2.1
 CALCULATION OF HEATING AND COOLING LOADS. SUBMIT 3 SETS
 OF CALCS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  