2017-02-03 10:35:02PLAN
 REVIEW COMMENTS
  
 6TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RESIDENTIAL BUILDING FORM R405 TO SHOW
 COMPLIANCE WITH THE ENERGY CODE THAT WAS SUBMITTED IS
 REQUIRED TO BE SIGNED AND DATED BY THE OWNER/AGENT. FBC
 ENERGY CONSERVATION R103.1.1.2
  
 2) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN
 PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO.
 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. THIS COMMENT
 HAS NOT BEEN ADDRESSED. ( IF YOU ELECT TO DO SO, THIS
 CAN BE SUBMITTED FOR REVIEW AT A LATER DATE. HOWEVER,
 IT WILL HAVE TO BE REVIEWED AND APPROVED BEFORE THE
 ROOFING IS INSTALLED. )
  
 3) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH
 COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
  
 4) ONE SET OF THE PLANS IS MISSING (4) PAGES. SUBMIT
 PLAN SHEETS T-1, D-1, P-1 AND E-1. 107.1 GENERAL.
 SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION
 DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS,
 GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED
 IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION.
  
  