Plan Review Notes
Plan Review Notes For Permit 16030072
Permit Number 16030072
Review Stop B
Sequence Number 5
Notes
Date Text
2016-12-16 18:25:35PLAN
 REVIEW COMMENTS
  
 5TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) AS WE DISCUSSED PREVIOUSLY, YOU HAVE INDICATED THAT
 YOU ARE NOT ABLE TO INSTALL THE REQUIRED R-30 CEILING
 INSULATION. THEREFORE, YOU CAN NOT USE THE PRESCRIPTIVE
 METHOD TO SHOW COMPLIANCE WITH THE FBC ENERGY
 CONSERVATION. YOU SUBMITTED MANUAL J CALCULATIONS WHICH
 ARE USED TO SIZE THE HEATING AND COOLING EQUIPMENT. YOU
 WERE REQUESTED TO SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS TO SHOW THAT THE BUILDING ENVELOPE MEETS THE FBC
 ENERGY CONSERVATION REQUIREMENTS. SUBMIT TWO SETS OF
 THE DOCUMENTS REQUIRED BY FBC ENERGY CONSERVATION
 SECTION R101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR
 COMPLIANCE BY SECTION R405.
  
 2) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN
 PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO.
 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. THIS COMMENT
 HAS NOT BEEN ADDRESSED. ( IF YOU ELECT TO DO SO, THIS
 CAN BE SUBMITTED FOR REVIEW AT A LATER DATE. HOWEVER,
 IT WILL HAVE TO BE REVIEWED AND APPROVED BEFORE THE
 ROOFING IS INSTALLED. )
  
 3) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH
 COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE.
  
  