2016-12-16 18:25:35 | PLAN |
| REVIEW COMMENTS |
| |
| 5TH REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) AS WE DISCUSSED PREVIOUSLY, YOU HAVE INDICATED THAT |
| YOU ARE NOT ABLE TO INSTALL THE REQUIRED R-30 CEILING |
| INSULATION. THEREFORE, YOU CAN NOT USE THE PRESCRIPTIVE |
| METHOD TO SHOW COMPLIANCE WITH THE FBC ENERGY |
| CONSERVATION. YOU SUBMITTED MANUAL J CALCULATIONS WHICH |
| ARE USED TO SIZE THE HEATING AND COOLING EQUIPMENT. YOU |
| WERE REQUESTED TO SUBMIT TWO SETS OF ENERGY COMPLIANCE |
| FORMS TO SHOW THAT THE BUILDING ENVELOPE MEETS THE FBC |
| ENERGY CONSERVATION REQUIREMENTS. SUBMIT TWO SETS OF |
| THE DOCUMENTS REQUIRED BY FBC ENERGY CONSERVATION |
| SECTION R101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) |
| DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR |
| COMPLIANCE BY SECTION R405. |
| |
| 2) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN |
| PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO. |
| 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS |
| 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY |
| LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. THIS COMMENT |
| HAS NOT BEEN ADDRESSED. ( IF YOU ELECT TO DO SO, THIS |
| CAN BE SUBMITTED FOR REVIEW AT A LATER DATE. HOWEVER, |
| IT WILL HAVE TO BE REVIEWED AND APPROVED BEFORE THE |
| ROOFING IS INSTALLED. ) |
| |
| 3) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH |
| COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE. |
| |
| |