2016-11-21 18:53:35 | PLAN |
| REVIEW COMMENTS |
| |
| 3RD REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW |
| ADDITION MEETS THE FBC ENERGY CONSERVATION |
| REQUIREMENTS. FBC ENERGY CONSERVATION R402.1 THE ENERGY |
| FORM R402-2014 THAT WAS SUBMITTED CONTAINS NUMEROUS |
| ERRORS AND OMISSIONS. THE OWNER'S NAME, BUILDER AND |
| PERMITTING OFFICE (WEST PALM BEACH) ARE NOT LISTED AT |
| THE TOP OF THE FORM. THE OWNER/AGENT SIGNATURE AND DATE |
| IS MISSING. ON PAGE TWO FOR THE FLOORS THE R-VALUE IS |
| SPECIFIED AS R-13. ON PAGE 1 FOR SLAB ON GRADE THE |
| R-VALUE SHOULD BE NR RATHER THAN NA. THE DUCTWORK IS |
| SPECIFIED AS R-16 ON PAGE 2 AND R-10 ON PAGE 1. THE |
| CEILING INSULATION IS SPECIFIED AS R-30, WHICH REQUIRES |
| MORE SPACE THAN THE 7-1/4 INCHES THAT THE 2 X 8 ROOF |
| JOISTS PROVIDE. SOME OF THE INSULATION R-VALUES |
| SPECIFIED ON THE PLANS DO NOT MATCH WHAT IS LISTED ON |
| THE FORM. |
| |
| 2) THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON |
| SHEET S-2 ARE INCORRECT. THIS STRUCTURE HAS A FLAT ROOF |
| AND A 14' ROOF HEIGHT PER THE PLANS. THE WIND SPEED IS |
| 170MPH VULT, 132MPH VASD. THE EXPOSURE CATEGORY IS C. |
| FBC-R301.2.1 FOR EXAMPLE: THE WORST CASE FOR A 10SQFT |
| AREA IN WALL ZONE 5 IS +37.9, -50.7 PSF IN EXPOSURE C, |
| 132MPH VASD WITH A 15' MEAN ROOF HEIGHT. (PREVIOUS |
| COMMENT) PLEASE HAVE A FLORIDA LICENSED ENGINEER REVIEW |
| THE COMPONENT AND CLADDING PRESSURES AND MAKE |
| CORRECTIONS TO THE PLANS. |
| |
| 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. (PREVIOUS COMMENT) THE PRODUCT |
| APPROVALS ARE REQUIRED TO BE APPROVED IN WRITING BY THE |
| ARCHITECT. |
| |
| 4) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN |
| PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO. |
| 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS |
| 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY |
| LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. |
| |
| 5) THE MASTER BEDROOM IS MISLABELED AS THE MASTER |
| BATHROOM ON A-1. FBC 107.2.1 |
| |
| 6) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR |
| THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4 |
| (PREVIOUS COMMENT) THERE IS NO FL NUMBER ON THE DOOR |
| PRODUCT APPROVALS. |
| |
| 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |