Plan Review Notes
Plan Review Notes For Permit 16030072
Permit Number 16030072
Review Stop B
Sequence Number 3
Notes
Date Text
2016-11-21 18:53:35PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW
 ADDITION MEETS THE FBC ENERGY CONSERVATION
 REQUIREMENTS. FBC ENERGY CONSERVATION R402.1 THE ENERGY
 FORM R402-2014 THAT WAS SUBMITTED CONTAINS NUMEROUS
 ERRORS AND OMISSIONS. THE OWNER'S NAME, BUILDER AND
 PERMITTING OFFICE (WEST PALM BEACH) ARE NOT LISTED AT
 THE TOP OF THE FORM. THE OWNER/AGENT SIGNATURE AND DATE
 IS MISSING. ON PAGE TWO FOR THE FLOORS THE R-VALUE IS
 SPECIFIED AS R-13. ON PAGE 1 FOR SLAB ON GRADE THE
 R-VALUE SHOULD BE NR RATHER THAN NA. THE DUCTWORK IS
 SPECIFIED AS R-16 ON PAGE 2 AND R-10 ON PAGE 1. THE
 CEILING INSULATION IS SPECIFIED AS R-30, WHICH REQUIRES
 MORE SPACE THAN THE 7-1/4 INCHES THAT THE 2 X 8 ROOF
 JOISTS PROVIDE. SOME OF THE INSULATION R-VALUES
 SPECIFIED ON THE PLANS DO NOT MATCH WHAT IS LISTED ON
 THE FORM.
  
 2) THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON
 SHEET S-2 ARE INCORRECT. THIS STRUCTURE HAS A FLAT ROOF
 AND A 14' ROOF HEIGHT PER THE PLANS. THE WIND SPEED IS
 170MPH VULT, 132MPH VASD. THE EXPOSURE CATEGORY IS C.
 FBC-R301.2.1 FOR EXAMPLE: THE WORST CASE FOR A 10SQFT
 AREA IN WALL ZONE 5 IS +37.9, -50.7 PSF IN EXPOSURE C,
 132MPH VASD WITH A 15' MEAN ROOF HEIGHT. (PREVIOUS
 COMMENT) PLEASE HAVE A FLORIDA LICENSED ENGINEER REVIEW
 THE COMPONENT AND CLADDING PRESSURES AND MAKE
 CORRECTIONS TO THE PLANS.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. (PREVIOUS COMMENT) THE PRODUCT
 APPROVALS ARE REQUIRED TO BE APPROVED IN WRITING BY THE
 ARCHITECT.
  
 4) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN
 PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO.
 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA.
  
 5) THE MASTER BEDROOM IS MISLABELED AS THE MASTER
 BATHROOM ON A-1. FBC 107.2.1
  
 6) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR
 THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4
 (PREVIOUS COMMENT) THERE IS NO FL NUMBER ON THE DOOR
 PRODUCT APPROVALS.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.