2016-09-29 17:24:09PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW
 ADDITION MEETS THE FBC ENERGY CONSERVATION
 REQUIREMENTS. FBC ENERGY CONSERVATION R402.1
  
 2) SPECIFY HOW THE 3 MEMBER 2 X 8 BEAM WILL BE ANCHORED
 TO THE BLOCK WALL AND THE WOOD FRAME WALL AT EACH END.
 FBC 107.2.1 & R301.1
  
 3) REVISE THE ROOF FRAMING PLAN TO SHOW THE 12"
 OVERHANG FRAMING FOR ALL SIDES OF THE STRUCTURE. FBC
 107.2.1 & R301.1
  
 4) SHOW THE LOCATIONS OF THE VARIOUS ROOF CONNECTORS,
 HANGERS AND ANCHORS ON THE ROOF FRAMING PLAN. FOR
 CLARITY PROVIDE A ROOF FRAMING PLAN WITH CONNECTORS
 SPECIFIED AT PROPER LOCATIONS ON THE STRUCTURAL
 DRAWINGS. FBC 107.2.1 & 107.2.1.3
  
 5) THE ANCHOR SCHEDULE ON S-1, SPECIFIES AN A1 HANGER
 FOR A 6 X 12 TIMBER BEAM. THERE IS NO 6 X 12 BEAM
 SPECIFIED ON THE PLANS. PLEASE CLARIFY. FBC 107.2.1
  
 6) THERE IS AN A6 ANCHOR IN THE ANCHOR SCHEDULE AND
 THERE IS NO A6 TAG ON THE PLANS. IT APPEARS THAT THIS
 WAS MEANT TO BE THE A2 ANCHOR. PLEASE CLARIFY. FBC
 107.2.1
  
 7) THE 8D ROOF SHEATHING FASTENERS ARE REQUIRED TO BE
 RING-SHANK PER FBC-R803.2.3.1
  
 8) THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON
 SHEET S-2 ARE INCORRECT. THIS STRUCTURE HAS A FLAT ROOF
 AND A 14' ROOF HEIGHT PER THE PLANS. THE WIND SPEED IS
 170MPH VULT, 132MPH VASD. THE EXPOSURE CATEGORY IS C.
 FBC-R301.2.1 FOR EXAMPLE: THE WORST CASE FOR A 10SQFT
 AREA IN WALL ZONE 5 IS +37.9, -50.7 PSF IN EXPOSURE C,
 132MPH VASD WITH A 15' MEAN ROOF HEIGHT.
  
 9) ON SHEET S-2 THE BASIC WIND SPEED IS SPECIFIED AS
 180 MPH AND THE WIND SPEED FOR WEST PALM BEACH IS 170
 MPH VULT. FBC R301.2.1
  
 10) SPECIFY THE REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE NEW EXTERIOR DOOR ON THE PLANS.
 FBC-R301.2.1
  
 11) THE WRONG EDITIONS OF ACI 318 AND 530 ARE SPECIFIED
 ON S-2. THE FBC REFERENCES ACI 318 - 11 AND ACI 530 -
 11. FBC - R CHAPTER 46.
  
 12) THERE IS A 12" X 16" THICKENED EDGE MONOLITHIC
 FOOTING SHOWN ON S-1. THIS DOES NOT COMPLY WITH FBCR
 403.1.4 WHICH REQUIRES THE FOOTINGS TO BE AT LEAST 12
 INCHES BELOW GRADE AND FBCR 404.1.6 WHICH REQUIRES THE
 CONCRETE FOUNDATION TO EXTEND ABOVE THE FINISHED GRADE
 ADJACENT TO THE FOUNDATION AT ALL POINTS A MINIMUM OF 4
 INCHES (102 MM) WHERE MASONRY VENEER IS USED AND A
 MINIMUM OF 6 INCHES (152 MM) ELSEWHERE. (PREVIOUS
 COMMENT)
  
 13) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. (PREVIOUS COMMENT)
  
 14) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR
 NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND
 MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. FBC
 107.3.4 (PREVIOUS COMMENT)
  
 15) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR
 THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4
 (PREVIOUS COMMENT)
  
 16) SHEET A-1 IN ONE OF THE PLAN SETS DOES NOT HAVE THE
 ARCHITECT'S EMBOSSED SEAL. FBC 107.1 & FLORIDA STATUTES
 CHAPTER 481
  
 17) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.