2016-07-29 11:26:04 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS SPECIFY THIS PROJECT AS AN R-1 OCCUPANCY. |
| PLEASE CLARIFY THE OCCUPANCY TYPE. IF THIS IS A ONE OR |
| TWO FAMILY DWELLING THE OCCUPANCY TYPE IS R-3. |
| 310.3 RESIDENTIAL GROUP R-1. RESIDENTIAL OCCUPANCIES |
| CONTAINING SLEEPING UNITS WHERE THE OCCUPANTS ARE |
| PRIMARILY TRANSIENT IN NATURE, INCLUDING: |
| BOARDING HOUSES (TRANSIENT) WITH MORE THAN 10 OCCUPANTS |
| CONGREGATE LIVING FACILITIES (TRANSIENT) WITH MORE THAN |
| 10 OCCUPANTS |
| HOTELS (TRANSIENT) |
| MOTELS (TRANSIENT) |
| |
| 2) THE PLANS SPECIFY THE CONSTRUCTION AS TYPE III. TYPE |
| III CONSTRUCTION REQUIRES 2 HOUR FIRE RATED WALLS AMONG |
| OTHER THINGS THAT THIS STRUCTURE DOES NOT HAVE. THIS |
| APPEARS TO BE TYPE V-B CONSTRUCTION. PLEASE CLARIFY. |
| |
| 3) LABEL THE INTENDED USE OF THE NEW AREA ADJACENT TO |
| THE EXISTING UTILITY ROOM ON THE PLANS. FBC 107.2.1 |
| |
| 4) INDICATE THE USE OR ROOM TYPE OF THE LARGE UNLABELED |
| AREA ADJACENT TO BEDROOM #1 ON THE PLANS. FBC 107.2.1 |
| |
| 5) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW |
| ADDITION MEETS THE FBC ENERGY CONSERVATION |
| REQUIREMENTS. |
| |
| 6) SPECIFY THE WALL AND CEILING INSULATION R-VALUES ON |
| THE PLANS. |
| |
| 7) THE ROOF FRAMING PLAN ON SHEET A-1 HAS 2 X 8 WOOD |
| TRUSS. DID YOU INTEND THIS TO BE A WOOD JOIST OR A |
| TRUSS? IF THIS IS A SINGLE ASSEMBLY FLAT ROOF SYSTEM, |
| THERE ARE NO CEILING JOISTS. THERE WOULD BE ONLY ROOF |
| RAFTERS WITH THE CEILING ATTACHED TO THE BOTTOM OF |
| THEM. PLEASE CLARIFY ON THE PLANS. |
| |
| 8) THE ROOF FRAMING PLAN ON SHEET A-1 SPECIFIES A (3) 2 |
| X 10 WOOD BEAM. THE TWO DETAILS ON SHEET S-1 SHOW A (3) |
| 2 X 8 BEAM. PLEASE CORRECT. FBC 107.2.1 |
| |
| 9) SECTION A-A ON SHEET S-1 SHOWS THE BLOCK WALLS |
| EXTENDING TO THE UNDERSIDE OF THE ROOF SHEATHING. ONE |
| OF THE DETAILS ON S-1 SHOWS THE (3) 2 X 8 BEAM ON TOP |
| OF THE BLOCK WALL. PLEASE CORRECT THE INCONSISTENCIES. |
| |
| 10) ONE OF THE DETAILS ON S-1 SHOWS THE RAFTERS BUTTING |
| INTO THE (3) 2 X 8 BEAM. SPECIFY THE HANGERS THAT WILL |
| BE USED AND CLARIFY THE WOOD PLATE AND ANCHOR BOLT THAT |
| IS SHOWN ON TOP OF THE BEAM. |
| |
| 11) SPECIFY HOW THE 3 MEMBER 2 X BEAM WILL BE ANCHORED |
| TO THE BLOCK WALLS AT EACH END. |
| |
| 12) SHOW THE LOCATIONS OF THE VARIOUS ROOF CONNECTORS, |
| HANGERS AND ANCHORS ON THE ROOF FRAMING PLAN. FBC |
| 107.2.1 |
| |
| 13) SPECIFY THE ROOF SHEATHING FASTENERS AND SPACING ON |
| THE PLANS. |
| |
| 14) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE ROOF |
| COVERING FOR ROOF ZONES 1, 2 AND 3 ON THE PLANS. |
| |
| 15) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE NEW |
| EXTERIOR DOOR ON THE PLANS. |
| |
| 16) THE WINDOW SCHEDULE ON A-2 HAS HORIZONTAL SLIDING |
| WINDOWS LISTED AND THE PRODUCT APPROVALS ARE FOR SINGLE |
| HUNG WINDOWS. PLEASE CORRECT. |
| |
| 17) THERE IS A 12" X 16" THICKENED EDGE MONOLITHIC |
| FOOTING SHOWN ON S-1. THIS DOES NOT COMPLY WITH FBCR |
| 403.1.4 WHICH REQUIRES THE FOOTINGS TO BE AT LEAST 12 |
| INCHES BELOW GRADE AND FBCR 404.1.6 WHICH REQUIRES THE |
| CONCRETE FOUNDATION TO EXTEND ABOVE THE FINISHED GRADE |
| ADJACENT TO THE FOUNDATION AT ALL POINTS A MINIMUM OF 4 |
| INCHES (102 MM) WHERE MASONRY VENEER IS USED AND A |
| MINIMUM OF 6 INCHES (152 MM) ELSEWHERE. |
| |
| 18) FBCR 318.5 REQUIRES GUTTERS WITH DOWNSPOUTS ON ALL |
| BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. SPECIFY THE ROOF OVERHANG ON |
| THE PLANS. |
| |
| 19) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED |
| SMOKE ALARMS. |
| |
| 20) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. |
| |
| 21) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR |
| NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND |
| MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. FBC |
| 107.3.4 |
| |
| 22) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR |
| THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4 |
| |
| 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |