2016-07-29 11:26:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THIS PROJECT AS AN R-1 OCCUPANCY.
 PLEASE CLARIFY THE OCCUPANCY TYPE. IF THIS IS A ONE OR
 TWO FAMILY DWELLING THE OCCUPANCY TYPE IS R-3.
 310.3 RESIDENTIAL GROUP R-1. RESIDENTIAL OCCUPANCIES
 CONTAINING SLEEPING UNITS WHERE THE OCCUPANTS ARE
 PRIMARILY TRANSIENT IN NATURE, INCLUDING:
 BOARDING HOUSES (TRANSIENT) WITH MORE THAN 10 OCCUPANTS
 CONGREGATE LIVING FACILITIES (TRANSIENT) WITH MORE THAN
 10 OCCUPANTS
 HOTELS (TRANSIENT)
 MOTELS (TRANSIENT)
  
 2) THE PLANS SPECIFY THE CONSTRUCTION AS TYPE III. TYPE
 III CONSTRUCTION REQUIRES 2 HOUR FIRE RATED WALLS AMONG
 OTHER THINGS THAT THIS STRUCTURE DOES NOT HAVE. THIS
 APPEARS TO BE TYPE V-B CONSTRUCTION. PLEASE CLARIFY.
  
 3) LABEL THE INTENDED USE OF THE NEW AREA ADJACENT TO
 THE EXISTING UTILITY ROOM ON THE PLANS. FBC 107.2.1
  
 4) INDICATE THE USE OR ROOM TYPE OF THE LARGE UNLABELED
 AREA ADJACENT TO BEDROOM #1 ON THE PLANS. FBC 107.2.1
  
 5) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW
 ADDITION MEETS THE FBC ENERGY CONSERVATION
 REQUIREMENTS.
  
 6) SPECIFY THE WALL AND CEILING INSULATION R-VALUES ON
 THE PLANS.
  
 7) THE ROOF FRAMING PLAN ON SHEET A-1 HAS 2 X 8 WOOD
 TRUSS. DID YOU INTEND THIS TO BE A WOOD JOIST OR A
 TRUSS? IF THIS IS A SINGLE ASSEMBLY FLAT ROOF SYSTEM,
 THERE ARE NO CEILING JOISTS. THERE WOULD BE ONLY ROOF
 RAFTERS WITH THE CEILING ATTACHED TO THE BOTTOM OF
 THEM. PLEASE CLARIFY ON THE PLANS.
  
 8) THE ROOF FRAMING PLAN ON SHEET A-1 SPECIFIES A (3) 2
 X 10 WOOD BEAM. THE TWO DETAILS ON SHEET S-1 SHOW A (3)
 2 X 8 BEAM. PLEASE CORRECT. FBC 107.2.1
  
 9) SECTION A-A ON SHEET S-1 SHOWS THE BLOCK WALLS
 EXTENDING TO THE UNDERSIDE OF THE ROOF SHEATHING. ONE
 OF THE DETAILS ON S-1 SHOWS THE (3) 2 X 8 BEAM ON TOP
 OF THE BLOCK WALL. PLEASE CORRECT THE INCONSISTENCIES.
  
 10) ONE OF THE DETAILS ON S-1 SHOWS THE RAFTERS BUTTING
 INTO THE (3) 2 X 8 BEAM. SPECIFY THE HANGERS THAT WILL
 BE USED AND CLARIFY THE WOOD PLATE AND ANCHOR BOLT THAT
 IS SHOWN ON TOP OF THE BEAM.
  
 11) SPECIFY HOW THE 3 MEMBER 2 X BEAM WILL BE ANCHORED
 TO THE BLOCK WALLS AT EACH END.
  
 12) SHOW THE LOCATIONS OF THE VARIOUS ROOF CONNECTORS,
 HANGERS AND ANCHORS ON THE ROOF FRAMING PLAN. FBC
 107.2.1
  
 13) SPECIFY THE ROOF SHEATHING FASTENERS AND SPACING ON
 THE PLANS.
  
 14) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE ROOF
 COVERING FOR ROOF ZONES 1, 2 AND 3 ON THE PLANS.
  
 15) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE NEW
 EXTERIOR DOOR ON THE PLANS.
  
 16) THE WINDOW SCHEDULE ON A-2 HAS HORIZONTAL SLIDING
 WINDOWS LISTED AND THE PRODUCT APPROVALS ARE FOR SINGLE
 HUNG WINDOWS. PLEASE CORRECT.
  
 17) THERE IS A 12" X 16" THICKENED EDGE MONOLITHIC
 FOOTING SHOWN ON S-1. THIS DOES NOT COMPLY WITH FBCR
 403.1.4 WHICH REQUIRES THE FOOTINGS TO BE AT LEAST 12
 INCHES BELOW GRADE AND FBCR 404.1.6 WHICH REQUIRES THE
 CONCRETE FOUNDATION TO EXTEND ABOVE THE FINISHED GRADE
 ADJACENT TO THE FOUNDATION AT ALL POINTS A MINIMUM OF 4
 INCHES (102 MM) WHERE MASONRY VENEER IS USED AND A
 MINIMUM OF 6 INCHES (152 MM) ELSEWHERE.
  
 18) FBCR 318.5 REQUIRES GUTTERS WITH DOWNSPOUTS ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF. SPECIFY THE ROOF OVERHANG ON
 THE PLANS.
  
 19) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED
 SMOKE ALARMS.
  
 20) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 21) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR
 NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND
 MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. FBC
 107.3.4
  
 22) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR
 THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  