Plan Review Notes
Plan Review Notes For Permit 16030058
Permit Number 16030058
Review Stop B
Sequence Number 3
Notes
Date Text
2016-05-14 12:26:53****PROVISOS****
 ****ISSUED AT CONTRACTOR'S RISK****
 ***REVISED 6/23/16; ADDED RE-PLAT TO PROVISO #2
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL
 OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 2. A UNITY OF TITLE OR RE-PLAT IS REQUIRED FOR
 COMPLIANCE WITH FBC 705.8. WHEN AVAILABLE, PROVIDE THE
 BOOK AND PAGE WHERE THIS HAS BEEN RECORDED OR PROVIDE A
 COPY OF THE RECORDED UNITY OF TITLE OR RE-PLAT
 (REQUIRED PRIOR TO C.O.).
  
 3. REVISION REQUIRED:
 A. PROVIDE REVISED SHEET A100.
 B. THE WIND TUNNEL REPORT SUBMITTED IS NOT SIGNED AND
 SEALED AND IS AN "INTERIM" REPORT RATHER THAN THE
 "FINAL STRUCTURAL LOADS REPORT." PROVIDE THE DIGITALLY
 SIGNED AND SEALED FINAL STRUCTURAL LOADS REPORT.
  
 4. PER DOR, NV5 HAS REVIEWED THE FOUNDATION DESIGN PER
 THEIR RECOMMENDATION AND WILL MONITOR THE AUGERCAST
 PILE INSTALLATION.
  
  
  