2016-03-17 17:01:14 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| GOVERNING CODE: FBC 5TH EDITION (FBC 2014) |
| |
| 1. FLORIDA STATUTE 553.71, THIS BUILDING QUALIFIES AS A |
| THRESHOLD BUILDING; ANY BUILDING WHICH IS GREATER THAN |
| (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED: |
| |
| A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), 2010 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE |
| ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY |
| THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS |
| 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY |
| THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED |
| TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT |
| ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL |
| INFORMATION. |
| FORMS WERE SENT TO : [email protected], |
| [email protected] ON 3/17/16. |
| |
| C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF |
| INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW |
| BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE |
| RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE |
| RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY |
| SAMANTHA HILL), 561-805-6666, [email protected], |
| [email protected] |
| |
| ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE |
| CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN |
| THE SPECIAL INSPECTOR AGREEMENT. |
| |
| D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY |
| FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL |
| ([email protected], [email protected]). |
| |
| E. SEE FLORIDA STATUTE 553.79 (7)(D); ALL PLANS FOR THE |
| BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND CHAPTER |
| 633. |
| |
| I WAS UNABLE TO LOCATE THIS STATEMENT (ARCHITECT, |
| ENGINEER), PLEASE REVISE PLANS TO INCLUDE. |
| |
| |
| |
| |