Plan Review Notes
Plan Review Notes For Permit 16030058
Permit Number 16030058
Review Stop THRESHOLD
Sequence Number 1
Notes
Date Text
2016-03-17 17:01:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, THIS BUILDING QUALIFIES AS A
 THRESHOLD BUILDING; ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO : [email protected],
 [email protected] ON 3/17/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. SEE FLORIDA STATUTE 553.79 (7)(D); ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND CHAPTER
 633.
  
 I WAS UNABLE TO LOCATE THIS STATEMENT (ARCHITECT,
 ENGINEER), PLEASE REVISE PLANS TO INCLUDE.
  
  
  
  