2016-03-31 12:37:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1. SHEET 0103 C301 AAF TOD - ONLY ONE (1) WATER SUPPLY |
| WAS NOTED ON THE DRAWING. |
| |
| NFPA 1, 18.3 WATER SUPPLIES. |
| 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING |
| THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE |
| PROVIDED TO ALL PREMISES UPON WHICH FACILITIES, |
| BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER |
| CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE |
| APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH |
| SECTION 18.4. |
| |
| NFPA 101, 1.8 FLORIDA FIRE PREVENTION CODE AND FLORIDA |
| BUILDING CODE INTERRELATION. THE FLORIDA FIRE |
| PREVENTION CODE CONTAINS SEVERAL PROVISIONS AND |
| REQUIREMENTS THAT MAY INTERRELATE WITH THE FLORIDA |
| BUILDING CODE. IT IS NOT THE INTENT OF THIS CODE THAT |
| SUCH INTERRELATION RESULT IN DUPLICATE REVIEWS AND |
| INSPECTIONS BY EITHER THE FIRESAFETYAUTHORITY OR THE |
| BUILDING OFFICIAL. THE AUTHORITY HAVING JURISDICTION |
| OVER FIRESAFETY IS RESPONSIBLE FOR ENFORCEMENT OF THE |
| FLORIDA FIRE PREVENTION CODE HEREOF, AND, IN THE EVENT |
| THAT A DISPUTE ARISES REGARDING THE ENFORCEMENT OF THE |
| FLORIDA FIRE PREVENTION CODE AS RELATED TO THE |
| ENFORCEMENT OF THE FLORIDA BUILDING CODE, THE AUTHORITY |
| HAVING JURISDICTION OVER FIRESAFETY SHALL RESOLVE THE |
| DISPUTE BY THE PROCEDURE SET FORTH IN CHAPTER 633 AND |
| CHAPTER 553, FLORIDA STATUTES, AS REQUIRED BY SECTION |
| 633.104(5), FLORIDA STATUTES. |
| |
| PER FL BLDG CODE 5TH ED. SECTION 403 HIGH-RISE |
| BUILDINGS |
| 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS. REQUIRED |
| FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO NO FEWER |
| THAN TWO WATER MAINS LOCATED IN DIFFERENT STREETS. |
| SEPARATE SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH |
| CONNECTION TO THE WATER MAIN AND THE PUMPS. EACH |
| CONNECTION AND THE SUPPLY PIPING BETWEEN THE CONNECTION |
| AND THE PUMPS SHALL BE SIZED TO SUPPLY THE FLOW AND |
| PRESSURE REQUIRED FOR THE PUMPS TO OPERATE. |
| |
| PLEASE PROVIDE FOR TWO (2) SEPARATE WATER SUPPLIES. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |