Plan Review Notes
Plan Review Notes For Permit 16030008
Permit Number 16030008
Review Stop P
Sequence Number 2
Notes
Date Text
2016-04-27 05:04:201) SHOW THE LOCATION OF THE CONTROLLER AND THE REQUIRED
 RAIN SENSOR ON THE PLANS.FBC 107.2.1.
 2) A RAIN SENSOR IS REQUIRED ON THE SYSTEM PER FLA.
 STATUTE 373.62. THE NOTE "NO RAIN SENSOR" WRITTEN ON
 THE PLAN IS UNACCEPTABLE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  