2016-05-02 19:40:31 | ELECTRICAL REVIEW COMMENTS |
| |
| CORRECTIONS REQUIRED: |
| THERE CONTINUES TO BE NUMEROUS ABNORMALITIES WITH THIS |
| SUBMITTAL. IT IS NOT MY INTENT TO GENERATE A PUNCH FOR |
| THE DESIGNER. JUST TO NAME A FEW OF THE DEFICIENCIES |
| NOTED, THE SCOPE OF WORK AS DEFINED FOR THIS REVISION |
| ALONG WITH THE SCOPE OF WORK DESCRIBED ON THE MASTER |
| PERMIT DO NOT MATCH WHAT IS INDICATED ON THE SUBMITTED |
| DRAWINGS. THOUGH THE RISER DIAGRAM HAS BEEN REVISED TO |
| INDICATE A SINGLE METER, THE ELECTRICAL PANELS |
| REFERENCED ARE NOT SHOWN ON THE FLOOR PLANS. YOU |
| SUBMITTED LOAD CALCS FOR A 150 AMP PANEL NOT SHOWN ON |
| THE RISER DIAGRAM. THE RISER DIAGRAM IS INDICATED TO BE |
| 300 AMP WITH A 200 AMP RATED CONDUCTOR. |
| YOU NEED TO SUBMIT A SITE SPECIFIC RISER DIAGRAM AS |
| INDICATED IN NEC 215.5. |
| THE ELECTRICAL OUTLETS AND LIGHTING AS SHOWN ON THE |
| FLOOR PLAN FOR BLDG. 1 FAIL TO MEET MINIMUM CODE |
| REQUIREMENTS AS WELL. VERIFY OUTLET SPACING AS |
| INDICATED IN NEC 210.52. PLEASE REMEMBER TO PROVIDE |
| PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| PLEASE NOTE THAT THIS IS NOT THE FIRST TIME THIS COMES |
| UP FOR REVIEW. THE MASTER PERMIT WAS REVIEWED 6 TIMES |
| AND STILL NEVER WAS PROPERLY PRESENTED. |
| AT THIS TIME I WOULD LIKE TO MAKE YOU AWARE OF THE |
| FOLLOWING: |
| PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT |
| WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY |
| PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON |
| ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A |
| PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO |
| THE NORMAL FEE |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |