2016-05-02 19:40:31ELECTRICAL REVIEW COMMENTS
  
 CORRECTIONS REQUIRED:
 THERE CONTINUES TO BE NUMEROUS ABNORMALITIES WITH THIS
 SUBMITTAL. IT IS NOT MY INTENT TO GENERATE A PUNCH FOR
 THE DESIGNER. JUST TO NAME A FEW OF THE DEFICIENCIES
 NOTED, THE SCOPE OF WORK AS DEFINED FOR THIS REVISION
 ALONG WITH THE SCOPE OF WORK DESCRIBED ON THE MASTER
 PERMIT DO NOT MATCH WHAT IS INDICATED ON THE SUBMITTED
 DRAWINGS. THOUGH THE RISER DIAGRAM HAS BEEN REVISED TO
 INDICATE A SINGLE METER, THE ELECTRICAL PANELS
 REFERENCED ARE NOT SHOWN ON THE FLOOR PLANS. YOU
 SUBMITTED LOAD CALCS FOR A 150 AMP PANEL NOT SHOWN ON
 THE RISER DIAGRAM. THE RISER DIAGRAM IS INDICATED TO BE
 300 AMP WITH A 200 AMP RATED CONDUCTOR.
 YOU NEED TO SUBMIT A SITE SPECIFIC RISER DIAGRAM AS
 INDICATED IN NEC 215.5.
 THE ELECTRICAL OUTLETS AND LIGHTING AS SHOWN ON THE
 FLOOR PLAN FOR BLDG. 1 FAIL TO MEET MINIMUM CODE
 REQUIREMENTS AS WELL. VERIFY OUTLET SPACING AS
 INDICATED IN NEC 210.52. PLEASE REMEMBER TO PROVIDE
 PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL.
 PLEASE NOTE THAT THIS IS NOT THE FIRST TIME THIS COMES
 UP FOR REVIEW. THE MASTER PERMIT WAS REVIEWED 6 TIMES
 AND STILL NEVER WAS PROPERLY PRESENTED.
 AT THIS TIME I WOULD LIKE TO MAKE YOU AWARE OF THE
 FOLLOWING:
 PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT
 WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY
 PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON
 ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A
 PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO
 THE NORMAL FEE
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved