2016-04-12 15:09:00ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 2010 FLORIDA BLDG. CODES; 2008 NEC
  
 CORRECTIONS REQUIRED
 ACCORDING TO THE PROPERTY APPRAISER THIS SITE IS ZONED
 AS SINGLE FAMILY AND UNTIL ZONING TELLS ME OTHERWISE A
 SECOND OR THIRD ELECTRICAL METER TO THIS SITE WILL NOT
 BE AUTHORIZED. IF MORE THAN A SINGLE METER IS
 AUTHORIZED, FPL STANDARDS PERMIT ONLY A SINGLE DROP PER
 LOT AND NEC HAS FURTHER LIMITATIONS SUCH AS THE
 GROUPING OF ALL DISCONNECTS; AND A SINGLE SERVICE TO A
 BLDG. AS WELL. THEREFORE, YOU SHALL REVISE THE SERVICE
 RISER DIAGRAM ACCORDINGLY.
 THAT BEING SAID AND ADDRESSED, THERE ARE FURTHER ISSUES
 TO COMPLY WITH SHOULD THE SERVICE MATTER GET SOLVED.
 NEC 314.27(D) REQUIRES THAT ALL CEILING BOXES USED TO
 SUPPORT PADDLE FANS BE LISTED FOR THE PURPOSE.
 NEC 110.26(D) REQUIRES THERE BE PROPER ILLUMINATION
 ABOUT THE ELECTRICAL PANEL.
 NEC 210.52(F) REQUIRES THAT A LAUNDRY CIRCUIT BE
 PROVIDED AND INCLUDED IN THE LOAD CALCS AND INCLUDED IN
 THE PANEL SCHEDULE.
 FBC-E SECTION 404.1 REQUIRES THAT A MINIMUM OF 50% OF
 THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
2016-03-24 12:46:06THIS FILE WAS NOT IN R11 WHEN I WENT FOR IT.
2016-03-03 10:36:59NEW REVISED DRAWINGS SUBMITTED. JG.