Plan Review Notes
Plan Review Notes For Permit 16020992
Permit Number 16020992
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-03 09:34:171ST REVIEW 2014 5TH FBC ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 -PLEASE PROVIDE A ELECTRICAL FLOOR PLAN SHOWING NEW
 WORK AND EXISTING LOCATION OF ELECTRICAL SYSTEM. WBA
 107
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 SMOKE/CARBON ALARMS REQUIRED PER RESIDENTIAL CODE
 SECTIONS 314 & 315
  
 OUTLETS TO BE AFCI PROTECTED PER NEC 210.12 B AND
 RECEPTACLES MUST BE TAMPER RESISTANT RATED ACCORDING TO
 NEC 406.11
  
 PROVIDE GFCI PROTECTION IN THOSE AREAS COVERED IN NEC
 210.8 A
  
  