Plan Review Notes For Permit 16020992 |
Permit Number |
16020992 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-03 09:34:17 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011/RESIDENTIAL | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | -PLEASE PROVIDE A ELECTRICAL FLOOR PLAN SHOWING NEW | | WORK AND EXISTING LOCATION OF ELECTRICAL SYSTEM. WBA | | 107 | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | FLOOR PLAN. | | | | SMOKE/CARBON ALARMS REQUIRED PER RESIDENTIAL CODE | | SECTIONS 314 & 315 | | | | OUTLETS TO BE AFCI PROTECTED PER NEC 210.12 B AND | | RECEPTACLES MUST BE TAMPER RESISTANT RATED ACCORDING TO | | NEC 406.11 | | | | PROVIDE GFCI PROTECTION IN THOSE AREAS COVERED IN NEC | | 210.8 A | | | | |
|