2016-03-18 11:35:27 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE PROVIDE AIC CALCULATIONS TO VERIFY EQUIPMENT | | RATINGS PER FBC RES E3606 AND FBC 107.3.5 | | 2. SHOW THE SERVICE MAIN PER FBC RES E3601.6.2. UNFUSED | | CONDUCTORS SHOWN THROUGH ATTIC NOT CONSIDERED NEAREST | | POINT OF ENTRY. MAIN TO BE READILY ACCESSIBLE NEAR THE | | POINT OF ENTRY. CORRELATE CHANGES WITH NOTES AT THE | | ONE-LINE DIAGRAM. | | 3. PROVIDE GENERAL NOTES TO INDICATE FBC EC 404.1- 75% | | OF LAMPS TO HIGH EFFICACY LAMPS AND SEPARATE PERMITS | | REQUIRED FOR LOW VOLTAGE SYSTEMS. | | 4. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|