2016-03-18 11:35:27INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE AIC CALCULATIONS TO VERIFY EQUIPMENT
 RATINGS PER FBC RES E3606 AND FBC 107.3.5
 2. SHOW THE SERVICE MAIN PER FBC RES E3601.6.2. UNFUSED
 CONDUCTORS SHOWN THROUGH ATTIC NOT CONSIDERED NEAREST
 POINT OF ENTRY. MAIN TO BE READILY ACCESSIBLE NEAR THE
 POINT OF ENTRY. CORRELATE CHANGES WITH NOTES AT THE
 ONE-LINE DIAGRAM.
 3. PROVIDE GENERAL NOTES TO INDICATE FBC EC 404.1- 75%
 OF LAMPS TO HIGH EFFICACY LAMPS AND SEPARATE PERMITS
 REQUIRED FOR LOW VOLTAGE SYSTEMS.
 4. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  