2 |
|
Notes |
Date |
Text |
2016-06-08 15:28:42 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | NEC 230.70(A)(1)/E3601.6.2 -THE SERVICE DISCONNECTING | | MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE | | LOCATION EITHER OUTSIDE OF A BUILDING OR STRUCTURE OR | | INSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE | | CONDUCTORS. UNLESS FEEDER RACEWAYS ARE BEING RANNED | | UNDERGROUND THEN THEY ARE CONSIDERED OUTSIDE THE | | BUILDING | | | | NEC 210.12B/E3902.12 - OUTLETS TO BE AFCI PROTECTED ( | | MAKE A NOTE ) | | | | FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE | | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN | | ONLY HIGH EFFICACY LAMPS. | | | | FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING | | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC | | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN | | CONDITIONED & UNCONDITIONED SPACES. |
|