Plan Review Notes For Permit 16020945 |
Permit Number |
16020945 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-17 09:36:53 | ROOFING REVIEW: | | | | 1-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.002(33) FOR: | | A) SHINGLES AS SPECIFIED ON PLANS (IF RE-ROOFING THE | | GUEST HOUSE). | | | | 2- BREEZEWAY FLAT ROOF NOA 12-0601.10 SUBMITTED: | | A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. | | SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN | | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION | | (2014). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|