Plan Review Notes
Plan Review Notes For Permit 16020945
Permit Number 16020945
Review Stop P
Sequence Number 1
Notes
Date Text
2016-02-27 11:21:571) SUBMIT A SANITARY RISER FOR REVIEW FOR THE CHANGES
 BEING MADE TO THE PLUMBING SYSTEM. FBC 107.3.5.3.
 2) THE WATER SUPPLY VALVES FOR THE STACKED WASHER/DRYER
 SHALL BE PROVIDED WITH ACCESS. THEY CANNOT BE LOCATED
 BEHIND THE UNIT UNLESS THERRE IS AN ACCESS PANEL IN THE
 UNIT. 2014 FBCR SEC.P2903.9.3.
 3) SUBMIT A GAS RISER FOR REVIEW FOR THE TANKLESS WATER
 HEATERS OR PLACE A NOTE ON THE PLUMBING SHEET THAT THE
 GAS WILL BE UNDER A SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR