Plan Review Notes
Plan Review Notes For Permit 16020945
Permit Number 16020945
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-01 08:21:28APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE NOTE THAT ZONING WILL NEED TO APPROVE 2
 ELECTRICAL METERS AS SHOWN, TO THIS SINGLE FAMILY
 DWELLING. AT THIS TIME A SINGLE METER ARRANGEMENT WILL
 NEED TO BE SHOWN. FBC 107.3.5
 2.SHOW ONE-LINE RISER DIAGRAM WITH ALL ASSOCIATED
 INFORMATION, EXAMPLE FEEDER CONDUCTOR SIZES ETC. FBC
 107.3.5
 3.LABEL ELECTRICAL EQUIPMENT?S AIC RATINGS, SERVICE AND
 PANEL BOARDS. FBC RES E3404.2.
 4.PROVIDE A NOTE TO REFLECT FBC RES E4002.14
 RECEPTACLES TO BE LISTED TAMPER RESISTANT.
 5.FBC RES 314 REQUIRES THE INTERCONNECTION OF SMOKE
 DETECTOR DEVICES UNLESS EXCEPTIONS ARE MET. PROVIDE A
 NOTE INDICATING REQUIREMENTS.
 6.SHOW THE REQUIRED CLEARANCE FOR THE PANEL BOARD SHOWN
 IN CLOSET AREA PER FBC RES E3405.1
 7.RECEPTACLE SPACING TO BE PROVIDED PER FBC RES
 E3901.2.2 WALL SPACE: SEE LIVING ROOM AREA AND BEDROOM.
 8.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL; PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  