2016-02-25 11:30:17 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THERE ARE TWO BUILDINGS ON THIS PROPERTY. INDICATE | | WHICH ONE OF THE BUILDINGS IS TO BE RE-ROOFED. | | FBC107.2.1 | | | | 2) PROVIDE TWO COPIES OF A ROOF DIAGRAM WITH | | DIMENSIONS, LOCATIONS OF SCUPPERS, ROOF SLOPE, PARAPET | | HEIGHTS ON ALL SIDES AND ANY OTHER RELAVENT | | INFORMATION. FBC 107.2.1 | | | | 3) THE FASTENER SPACING ON SECTION C OF THE FORM THAT | | YOU SUBMITTED DOES NOT MATCH THE SPACING SPECIFIED ON | | PAGE 23 OF THE NOA. THE MAXIMUM DESIGN PRESSURE ON PAGE | | 23 IS NEGATIVE 52.5 PSF. SPECIFY THE REQUIRED DESIGN | | PRESSURES FOR THE THREE ROOF ZONES ON THE ROOF DRAWING. | | IF THE REQUIRED PRESSURES ARE MORE THAN -52.5 PSF, THEN | | SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FOR THE | | ENHANCED FASTENING AS REQUIRED BY LIMITATION #7 ON PAGE | | 42 OF THE NOA NO.14-0529.02. |
|