Plan Review Notes
Plan Review Notes For Permit 16020902
Permit Number 16020902
Review Stop P
Sequence Number 2
Notes
Date Text
2016-05-09 05:39:151) SHOW THE INSIDE CLEAR DIMENSIONS FOR THE TOILET ROOM
 AND SHOW THE REQUIRED FLOOR CLEARANCES FOR THE PLUMBING
 FIXTURES PER THE 2014 FBC-PLUMBING SEC.405.3.1. 2ND
 REQUEST.
 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. FBC
 107.3.5.1.3. 2ND REQUEST.
 4) SIZE ALL SECTIONS OF THE SANITARY SYSTEM ON BOTH
 RISERS #1 & 2. 2ND REQUEST.
 5) THE ADDITION OF BATHROOM #5 CREATES A
 RECONFIGIURATION OF SPACE AND THEREFORE THIS IS
 CONSIDERED A LEVEL 2 ALTERATION, NOT A LEVEL 1. CORRECT
 THE PLAN.2014FEBC SEC.504.
 6) THERE ARE TWO IDENTICAL FLOOR PLAN SHEETS. REMOVE
 THE OLD SHEET AND SUBMIT THE LATEST REVISION. ANY
 PREVIOUS APPROVALS FROM PLAN REVIEWS MUST RE-REVIEW THE
 NEW SHEET.
  