Plan Review Notes For Permit 16020902 |
Permit Number |
16020902 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-05 06:33:04 | 1) PLACE THE OCCUPANCY TYPE OF THE BUILDING ON THE | | PLANS IN ACCORDANCE WITH CHAPT. 3 OF THE 2014 FBC. | | 2) THE NEW TOILET ROOM SHALL COMPLY WITH THE FL. | | ACCESSIBILITY CODE SEC.213.1, 213.2.SUBMIT THE INSIDE | | CLEAR DIMENSIONS FOR THE TOILET ROOM AND SHOW THE | | REQUIRED FLOOR CLEARANCES FOR THE PLUMBING FIXTURES PER | | THE 2014 FAC SECS.305, 604, 606.2. | | 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. FBC | | 107.3.5.1.3. | | 4) SIZE ALL SECTIONS OF THE SANITARY SYSTEM ON BOTH | | RISERS #1 3 2. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|