Plan Review Notes
Plan Review Notes For Permit 16020902
Permit Number 16020902
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-08 10:50:34NOTES CLEARED WITH DOUG H AND THE OWNER, COMMENTS NOT
 APPLICABLE
2016-03-02 09:46:35INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE PROVIDE A PANEL LOAD SCHEDULE REFLECTING LOADS
 AND BRANCH CIRCUIT CLEARLY IDENTIFIED FOR NEW EM
 LIGHTING. FBC 107.3.5
 2.SHOW PER NEC 700.12F THAT UNIT EQUIPMENT IS SERVED
 FROM THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCH.
 3.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU
 HAVE ANY QUESTIONS OR CONCERNS.
  
  
  